6 Parameters
6 - 30
E5@C Digital Temperature Controllers User’s Manual (H174)
This parameter sets the output dead band width for heating/cooling control. A negative setting sets an
overlapping band.
c-db
Dead Band
The control system must be set to heating/cooling
control.
• This parameter sets an area in which the control output is 0 centering around the set point
for a heating/cooling control.
of-r
Manual Reset Value
The control must be standard control and 2-PID
control.
The Integral Time parameter must be set to 0.
• This parameter sets the required manipulated variable to remove offset during
stabilization of P or PD control.
z
Related Parameters
Integral Time (Adjustment Level): Page 6-28
PID ON/OFF (Initial Setting Level): Page 6-44
Function
Setting
Setting range
Unit
Default
Temperature input
−
199.9 to 999.9
°
C or
°
F
0.0
Analog input
−
19.99 to 99.99
%FS
0.00
Function
Setting
Setting range
Unit
Default
0.0 to 100.0
%
50.0
See
See
Содержание E5C series
Страница 2: ......
Страница 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 98: ...3 Part Names and Basic Procedures 3 20 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Страница 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...