4 Basic Operation
4 - 6
E5@C Digital Temperature Controllers User’s Manual (H174)
After you have set the
icpt
(Initial Setting/Communications Protect) parameter to
0
(enable moving
to Advanced Function Setting Level), select
amov
(Move to Advanced Function Setting Level) in the
Initial Setting Level.
z
Moving to the Advanced Function Setting Level
z
Moving from the Advanced Function Setting Level to the Operation Level
Moving to the Advanced Function Setting Level after Clearing
Protection
1
Press the
O
Key for at least 3 seconds in the Operation Level.
The No. 1 display will flash when the key is pressed for 1 s or
longer. The display will change from the Operation Level to the
Initial Setting Level.
Operation Level
2
Press the
M
Key several times in the Initial Setting Level to
display
amoV
(Move to Advanced Function Setting Level).
Initial Setting Level
3
Press the
D
and
U
Keys at the Move to Advanced Function
Setting Level parameter and then enter
-169
.
*
You can hold the
U
(Up) or
D
(Down) Key to increment or decrement
the set value quickly.
Initial Setting Level
4
Press
M
Key once or wait for 2 seconds or longer without
doing anything.
The display will change to the Advanced Function Setting Level.
Advanced Function Setting
Level
1
Press the
O
Key for at least 1 second in the Advanced
Function Setting Level.
The display will change from the Advanced Function Setting Level
to the Initial Setting Level.
Advanced Function Setting
Level
2
Press the
O
Key for at least 1 second in the Initial Setting
Level.
Initial Setting Level
The display will change from the Initial Setting Level to the
Operation Level.
Operation Level
0
25
5
in-t
Input Type
0
amov
Move to Advanced
Function Setting
Level
-169
amov
Move to Advanced
Function Setting Level
−169: Password to
move to Advanced
Function Setting Level
off
init
Parameter
Initialization
off
init
5
in-t
Input Type
0
25
PV/SP
Содержание E5C series
Страница 2: ......
Страница 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 98: ...3 Part Names and Basic Procedures 3 20 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Страница 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...