![Omron E5C series Скачать руководство пользователя страница 187](http://html.mh-extra.com/html/omron/e5c-series/e5c-series_user-manual_742592187.webp)
5 - 39
5 Advanced Operations
E5@C Digital Temperature Controllers User’s Manual (H174)
5-14 U
s
ing
th
e Simpl
e
Pr
og
ra
m Fu
nct
ion
5
5-14-1 Simple Prog
ra
m Fun
c
tion
5-14 Using the Simple Program Function
• The simple program function can be used for the following type of control.
• The program will start when the Program Start parameter is changed from RSET to STRT. END will
be displayed on the No. 2 display and the output assigned as the program end output will turn ON
after the time set in the Soak Time parameter has expired in the wait band. The Program Pattern
parameter can be used to select moving to STOP mode or continuing operation in RUN mode after
the program ends.
z
Parameters Related to the Simple Program Function
* The setting unit of the Wait Band parameter is %FS for Controllers with Analog Inputs and the setting range is
OFF or 0.01 to 99.99.
z
Program Pattern
Either of two program patterns can be selected. The simple program operation will not be performed
if the Program Pattern parameter is set to OFF.
(1) Pattern 1 (STOP)
Control will stop and the STOP mode will be entered when the program has ended.
5-14-1 Simple Program Function
Parameter name
Display
Set (monitor) values
Unit
Display level
Program Pattern
ptrn
OFF, STOP, CONT
---
Initial Setting Level
Program Start
prst
RSET, STRT
---
Operation Level
Soak Time
soak
1 to 9999
min or h
Adjustment Level
Soak Time Unit
t-u
m (minutes)/h (hours)
---
Advanced Function
Setting Level
Wait Band
wt-b
OFF or 0.1 to 999.9*
°
C or
°
F*
Adjustment Level
Soak Time Remain
Monitor
sktr
0 to 9999
min or h
Operation Level
000
PV
SP
RSET
→
STRT
Set point
Wait band
Wait band
Soak time
END display
END output
Select either
STOP or RUN.
PV
SP
RSET
→
STRT
Set point
Wait band
Wait band
Soak time
END display
END output
Automatically switches from
RUN to STOP mode.
Содержание E5C series
Страница 2: ......
Страница 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 98: ...3 Part Names and Basic Procedures 3 20 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Страница 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...