![Omron E5C series Скачать руководство пользователя страница 248](http://html.mh-extra.com/html/omron/e5c-series/e5c-series_user-manual_742592248.webp)
6 Parameters
6 - 32
E5@C Digital Temperature Controllers User’s Manual (H174)
wt-b
Wait Band
The Program Pattern parameter must not be set to
OFF.
• This parameter sets the stable band within which the soak time is measured for the
simple program function.
z
Related Parameters
Program Start (Operation Level): Page 6-12
Soak Time Remain (Operation Level): Page 6-13
Soak Time (Adjustment Level): Page 6-31
Program Pattern (Initial Setting Level): Page 6-46
Soak Time Unit (Advanced Function Setting Level): Page 6-80
mV-s
MV at Stop
The control must be set to 2-PID control or a
Position-proportional Model must be used.
The MV at Stop and Error Addition parameter must
be ON.
• This parameter sets the MV to use when the RUN/STOP status changes from RUN to
STOP.
z
Related Parameters
RUN/STOP (Operation Level): Page 6-13
MV at Stop and Error Addition (Advanced Function Setting Level): Page 6-71
Close/Floating (Initial Setting Level): Page 6-57
Direct Setting of Position Proportional MV (Advanced Function Setting Level): Page 6-84
000
Function
Setting
Setting range
Unit
Unit
Temperature input
OFF or 0.1 to 999.9
°
C or
°
F
off
Analog input
OFF or 0.01 to 99.99
%FS
See
See
000
Function
Setting
Control method
Setting range
Unit
Default
Standard control
Close position-proportional control with the Direct Setting
of Position-proportional MV parameter set to ON
−
5.0 to 105.0
%
0.0
Heating/cooling control
−
105.0 to 105.0
Floating position-proportional control or the Direct Setting
of Position-proportional MV parameter set to OFF
CLOS, HOLD, or
OPEN
None
HOLD
See
See
Содержание E5C series
Страница 2: ......
Страница 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 98: ...3 Part Names and Basic Procedures 3 20 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Страница 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...