![Omron E5C series Скачать руководство пользователя страница 134](http://html.mh-extra.com/html/omron/e5c-series/e5c-series_user-manual_742592134.webp)
4 Basic Operation
4 - 36
E5@C Digital Temperature Controllers User’s Manual (H174)
z
SP Alarms
You can set an SP absolute-value upper-limit or SP absolute-value lower-limit alarm for the set point
(SP).
The alarm point is set in the corresponding alarm value parameter. The Alarm SP Selection
parameter is used to specify the alarm for either the ramp SP or the target SP.
The corresponding alarm hysteresis setting is also valid.
z
MV Alarms
You can set an MV absolute-value upper-limit or MV absolute-value lower-limit alarm for the
manipulated value (MV).
The alarm point is set in the corresponding alarm value parameter. The corresponding alarm
hysteresis setting is also valid.
z
RSP Alarms
You can set an RSP absolute-value upper-limit alarm or RSP absolute-value lower-limit alarm for the
remote SP input.
The alarm point is set in the corresponding alarm value parameter. The corresponding alarm
hysteresis setting is also valid.
SP absolute-value upper-limit alarm
SP absolute-value lower-limit alarm
The alarm output is ON while the SP is equal to or
higher than the set value.
The alarm output is ON while the SP is equal to or
lower than the set value.
MV absolute-value upper-limit alarm
MV absolute-value lower-limit alarm
The alarm output is ON while the MV is equal to or
higher than the set value.
The alarm output is ON while the MV is equal to or
lower than the set value.
RSP absolute-value upper-limit alarm
RSP absolute-value lower-limit alarm
The alarm output is ON while the remote SP is equal
to or higher than the set value.
The alarm output is ON while the remote SP is equal
to or lower than the set value.
ON
OFF
0
SP
Upper-limit alarm
point (e.g., 100
°
C)
Alarm value (e.g., 100
°
C)
Example:
ON
OFF
0
SP
Lower-limit alarm
point (e.g., 100
°
C)
Example:
Alarm value (e.g., 100
°
C)
ON
OFF
0
MV
Upper-limit alarm
point (e.g., 80%)
Alarm value (e.g., 80%)
Example for Standard Control:
ON
OFF
0
MV
Lower-limit alarm
point (e.g., 20%)
Example for Standard Control:
Alarm value (e.g., 20%)
000
ON
OFF
0
RSP
Upper-limit alarm
point (e.g., 100
°
C)
Alarm value (e.g., 100
°
C)
Example:
ON
OFF
0
RSP
Lower-limit alarm
point (e.g., 100
°
C)
Example:
Alarm value (e.g., 100
°
C)
Содержание E5C series
Страница 2: ......
Страница 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 98: ...3 Part Names and Basic Procedures 3 20 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Страница 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...