5 Advanced Operations
5 - 40
E5@C Digital Temperature Controllers User’s Manual (H174)
(2) Pattern 2 (CONT)
Control will continue in RUN mode when the program has ended.
z
Starting Method
Any of the following three methods can be used to start the simple program.
• Setting the Program Start parameter to STRT.
• Turning ON an event input. (The program start must be assigned to an event input.*)
• Starting with an Operation Command using communications. (When the program start is not
assigned to an event input.)
* When the simple program is started and reset, writing is performed to non-volatile memory. Be sure to consider
the write life (1 million writes) of the non-volatile memory in the system design. When the program start is
assigned to an event input, the Program Start parameter will function as a monitor display, and the
RSET/STRT displays can be used to check when the event input has started or reset the simple program.
When this is done, the Program Start parameter functions as a monitor display only and cannot be changed
using key operations. If the Program Pattern parameter is set to OFF, the event input assignment setting will be
initialized to "None."
z
Soak Time and Wait Band
The wait band is the band within which the process value is stable in respect to the set point. The
soak time is measured within the wait band. The timer that measures the soak time operates only
when the process value is within the wait band around the set point (i.e., SP
±
wait band). In the
above diagram, the timer will be stopped between the start and (1), (2) and (3), and (4) and (5) and
will measure the time only between (1) and (2), (3) and (4), and (5) and the end.
* If the wait band is set to OFF, the wait band will be treated as infinity and the timer will measure time
continuously after changing from RSET to STRT.
PV
SP
RSET
→
STRT
Set point
Wait band
Wait band
Soak time
END display
END output
RUN mode continues.
PV
RSET
→
STRT
(5)
(1)
(2) (3)
(4)
Set point
Wait band
Wait band
Soak time
remain
Set point
Set point
Содержание E5C series
Страница 2: ......
Страница 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 98: ...3 Part Names and Basic Procedures 3 20 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Страница 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...