5 Advanced Operations
E5@C Digital Temperature Controllers User’s Manual (H174)
5-8 Disp
la
yin
g
Onl
y P
aram
eter
s T
h
at Ha
ve B
een Ch
ang
ed
5
5-8-1 Displa
ying Chang
ed P
ar
a
meters
Precautions for Correct Use
• Set this parameter to ON only after making the required settings.
• The following parameters are displayed regardless of the setting of the Changed Parameters
Only parameter.
• Monitor parameters (including the PV, parameters with “monitor” in the parameter name and
the Set Point During SP Ramp parameter)
• Parameters that switch operation (RUN/STOP, Auto/Manual Switch, Multi-SP, Program Start,
AT Execute/Cancel, Communications Writing, SP Mode, Parameter Initialization, Copy, and
Motor Calibration).
• Level displays and parameters to move to other levels (such as Adjustment Level Display,
Move to Advanced Function Setting Level, and Move to Calibration Level)
• Manual MV
• Any parameters that are automatically initialized when another parameter is changed are
considered to be at their default settings.
Example: If the Input Type parameter is changed to 7, 850 is considered to be the default
setting of the Set Point Upper Limit parameter. Refer to A-6-9 Initialization
According to Parameter Changes for the parameters that are automatically
initialized.
• If the setting of a parameter is changed back to its default setting, it will no longer be displayed.
To display it again, set the Changed Parameters Only parameter to OFF.
• If a parameter is not displayed even when the Changed Parameters Only parameter is set to
OFF, check the conditions for the parameter.
• Use parameter masks to select the parameters to display without considering whether they
are set to their default settings. The CX-Thermo is required to set parameter masks.
Operating Procedure
1
Press the
M
Key several times in the Protect Level to display
chgp
(Changed Parameters Only).
Protect Level
2
Press the
U
or
D
Key to set the value to
on
.
Press the
O
+
M
Keys for at least 1 s to return to the Operation
Level. Only the parameters that have been changed from their
default settings will be displayed.
off
chgp
Changed
Parameters
Only
on
chgp
Содержание E5C series
Страница 2: ......
Страница 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 98: ...3 Part Names and Basic Procedures 3 20 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Страница 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...