6 Parameters
6 - 88
E5@C Digital Temperature Controllers User’s Manual (H174)
spd1
PV/SP No. 1 Display Selection
spd2
PV/SP No. 2 Display Selection
These parameters set the items to display on the No. 1 display, No. 2 display, and No. 3 dis-
play.
*
The Alarm Value 1 parameter is displayed even if the Alarm 1 Type parameter is set for no
alarm. However, any value that is set is not valid.
odsl
MV Display Selection
A Standard Model with a No. 3 display (E5EC/E5AC)
must be used and heating and cooling control must
be used. The PV/SP No. 1 Display Selection or
PV/SP No. 2 Display Selection parameter must be
set to 4, or the PF Setting parameter must be set to
PFDP and one of the monitor/setting items 1 to 5
must be set to 2.
• This parameter selects the MV display for PV/SP/MV during heating and cooling control.
Either heating MV or cooling MV can be selected.
Function
Setting
Set value
No. 1 display
No. 2 display
No. 3 display (E5EC/E5AC
only)
0
Nothing is displayed.
Nothing is displayed.
Nothing is displayed.
1
Process value
Set point
Nothing is displayed.
2
Process value
Nothing is displayed.
Nothing is displayed.
3
Set point
SP (character display)
Nothing is displayed.
4
Process value
Set point
MV (valve opening for
Position-proportional Models)
5
Process value
Set point
Multi-SP No.
6
Process value
Set point
Soak time remain
7
Process value
Set point
Internal set point (ramp SP)
8
Process value
Set point
Alarm value 1*
000
*
The default is 1 for models other than the E5
@
C-
@
-0
@
.
Parameter
Setting range
Default
PV/SP No. 1 Display Selection
0 to 8
4*
PV/SP No. 2 Display Selection
0
Function
Setting
Setting range
Default
o
: MV (heating)
c-o
: MV (cooling)
o
Содержание E5C series
Страница 2: ......
Страница 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 98: ...3 Part Names and Basic Procedures 3 20 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Страница 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...