4 - 17
4 Basic Operation
E5@C Digital Temperature Controllers User’s Manual (H174)
4-6 Setting Ou
tpu
t Sp
ecification
s
4
4-6-3 Assigned Output
Functio
ns
(Assig
ning C
ontrol Outputs Is
Not Suppor
ted f
or P
osition-p
ropor-
tional Models
.)
Assigned Output Functions
Controllers with Three or Fewer Auxiliary Outputs
Controllers with Four Auxiliary Outputs
*
If the Controller is equipped with HB/HS alarm detection, it is set by default to detect heater alarms (HA).
Therefore, the alarm 1 function is disabled and the Alarm 1 Type is not displayed. To enable alarm 1, set an
output assignment to alarm 1. If the Program Pattern parameter is changed to a setting other than OFF,
Auxiliary Output 1 Assignment parameter is set as the program end output.
z
Alarms
It will be specified in this section when an alarm must be assigned, i.e., when an alarm must be set
for the Control Output 1 or 2 Assignment parameters, or for the Auxiliary Output 1 to 4 Assignment
parameters. For example, if alarm 1 is set for the Control Output 1 Assignment parameter, then
alarm 1 has been assigned.
Assigning a work bit to either control output 1 or 2 or to auxiliary output 1 to 4 is also considered to
be the same as assigning an alarm. For example, if work bit 1 is set for the Auxiliary Output 1
Assignment parameter, then alarms 1 to 4 have been assigned.
Parameter name
Display
Without control output 2
With control output 2
Standard
Heating/cooling
Standard
Heating/cooling
Control Output 1
Assignment
out1
Control output
(heating)
Control output
(heating)
Control output
(heating)
Control output
(heating)
Control Output 2
Assignment
out2
---
---
Not assigned.
Control output
(cooling)
Auxiliary Output 1
Assignment
sub1
Alarm 1*
Alarm 1*
Alarm 1*
Alarm 1*
Auxiliary Output 2
Assignment
sub2
Alarm 2
Control output
(cooling)
Alarm 2
Alarm 2
Auxiliary Output 3
Assignment
sub3
Alarm 3
Alarm 3
Alarm 3
Alarm 3
Parameter name
Display
Without control output 2
With control output 2
Standard
Heating/cooling
Standard
Heating/cooling
Control Output 1
Assignment
out1
Control output
(heating)
Control output
(heating)
Control output
(heating)
Control output
(heating)
Control Output 2
Assignment
out2
---
---
Not assigned.
Control output
(cooling)
Auxiliary Output 1
Assignment
sub1
Alarm 1*
Alarm 1*
Alarm 1*
Alarm 1*
Auxiliary Output 2
Assignment
sub2
Alarm 2
Alarm 2
Alarm 2
Alarm 2
Auxiliary Output 3
Assignment
sub3
Alarm 3
Alarm 3
Alarm 3
Alarm 3
Auxiliary Output 4
Assignment
sub4
Alarm 4
Control output
(cooling)
Alarm 4
Alarm 4
Содержание E5C series
Страница 2: ......
Страница 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 98: ...3 Part Names and Basic Procedures 3 20 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Страница 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...