Chapter 4: MotionBlox-40R
NOTE:
112 mm clearance required in front of unit to remove amplifiers from
box enclosure.
Mounting Clearances
NOTE:
The mounting of the eMB-40R and all terminations at the eMB-40R
must be performed in accordance with all local and national standards.
The following space must be left around the eMB-40R for proper cooling:
100 / 200
50
1
2
3
Figure 4-9. Clearance for the eMB-40R (Units in mm)
Table 4-15. eMB-40R Clearance Description
Item
Surface
Air Gap
1
Back
0 mm
2
Sides
50 mm
3
Front, when wall-mounted
100 mm
Front, when flat-mounted
200 mm
NOTE:
These dimensions assume the eMB-40R has exposure to outside air,
rather than being in a sealed container. Any sealed container would need to
provide sufficient cooling for the eMB-40R’s internal fan to be effective.
05624-000 Rev. K
Cobra 350 User's Guide