345
Adjusting Offset and Gain
Section 7-9
The following example uses output number 1 adjustment for illustration. (The
unit number is 0.)
1,2,3...
1.
Turn ON bit 00 (the Offset Bit) of CIO word n+1. (Hold the ON status.)
2.
Check whether the output devices are connected.
3.
Monitor CIO word n+8 and check the set value while the Offset Bit is ON.
4.
Change the set value so that the output voltage are as shown in the follow-
ing table. The data can be set within the indicated ranges.
Output signal range
Possible output
voltage/current
adjustment
Output range
0 to 10 V
–0.5 to 0.5 V
FF38 to 00C8
(FE70 to 0190)
–10 to 10 V
–1.0 to 1.0 V
1 to 5 V
0.8 to 1.2 V
0 to 5 V
–0.25 to 0.25 V
4 to 20 mA
3.2 to 4.8 mA
(Values in parentheses are for a resolution of 8,000.)
CLR
000000 CT00
SHIFT
CONT
#
2
C
0
A
0
A
1
B
0
A
0
A
MON
200100 ^ OFF
SET
200100 ^ ON
A1
A2
Voltage output
Output 1
A2
A3
Current output
CLR
000000 CT00
SHIFT
CH
*DM
2
C
0
A
0
A
8
MON
2008 0000
Содержание CJ1W-AD041-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x TABLE OF CONTENTS...
Страница 15: ...xvi...
Страница 99: ...76 Handling Errors and Alarms Section 2 8...
Страница 191: ...168 Handling Errors and Alarms Section 4 8...
Страница 243: ...220 Handling Errors and Alarms Section 5 8...
Страница 381: ...358 Handling Errors and Alarms Section 7 10...
Страница 385: ...362 Dimensions Appendix A...
Страница 395: ...372 Sample Programs Appendix B...
Страница 396: ...373 Appendix C Data Memory Coding Sheets...
Страница 417: ...394 Data Memory Coding Sheets Appendix C...
Страница 425: ......