Handling Errors and Alarms
Section 4-8
ERC Indicator and RUN Indicator: Lit, ADJ Indicator: Flashing
This alarm will occur in the case of incorrect operation while in the adjustment
mode. In adjustment mode, the Adjustment Mode ON Flag will turn ON in bit
15 of CIO word n+9.
Note
When a PLC error occurs in the adjustment mode, Unit operations will stop
operating. (The input and output values immediately prior to the error will be
held.)
ERC Indicator: Lit, RUN Indicator: Not Lit
The ERC indicator will be lit when the initial settings for the Analog Output
Unit are not set correctly. The alarm flags for the following errors will turn ON
in CIO word n+9. These alarm flags will turn OFF when the error is cleared
and the Unit is restarted, or the Special I/O Unit Restart Bit is turned ON and
then OFF again.
Note
Bit 15 is normally turned OFF (i.e., set to 0).
4-8-3
Errors in the CPU Unit
When errors occur in the CPU Unit or I/O bus, and I/O refresh with the Special
I/O Unit is not performed correctly resulting in the Analog Output Unit mal-
functioning, the ERH indicator will be lit.
ERH and RUN Indicators: Lit
RUN
ERC
ERH
ADJ
: Lit
: Flashing
: Not lit
Word n + 9
Alarm flag
Error contents
Output status
Countermeasure
Bit 13
(Adjustment
mode)
Output Number
Setting Error
In adjustment mode, adjust-
ment cannot be performed
because the specified output
number is not set for use or
because the wrong output num-
ber is specified.
The output volt-
age or current
becomes 0 V or
0 mA.
Check whether the word n out-
put number to be adjusted is set
from 11 to 14.
Check whether the output num-
ber to be adjusted is set for use
by means of the DM setting.
Bit 15 only ON
(Adjustment
Mode)
PLC Error
The PLC is in either MONITOR
or RUN mode while the Analog
Output Unit is operating in
adjustment mode.
The output volt-
age or current
becomes 0 V or
0 mA.
Detach the Unit. Switch the rear
panel DIP switch pin to OFF.
Restart the Unit in normal mode.
RUN
ERC
ERH
: Lit
: Not lit
Word n + 9
Alarm flag
Error contents
Countermeasure
Bit 10
Output Hold
Setting Error
The wrong output status for when conver-
sion is stopped has been specified.
Specify a number from 0000 to 0002.
RUN
ERC
ERH
: Lit
: Not lit
Содержание CJ1W-AD041-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x TABLE OF CONTENTS...
Страница 15: ...xvi...
Страница 99: ...76 Handling Errors and Alarms Section 2 8...
Страница 191: ...168 Handling Errors and Alarms Section 4 8...
Страница 243: ...220 Handling Errors and Alarms Section 5 8...
Страница 381: ...358 Handling Errors and Alarms Section 7 10...
Страница 385: ...362 Dimensions Appendix A...
Страница 395: ...372 Sample Programs Appendix B...
Страница 396: ...373 Appendix C Data Memory Coding Sheets...
Страница 417: ...394 Data Memory Coding Sheets Appendix C...
Страница 425: ......