131
Operating Procedure
Section 4-2
Offset and Gain Adjustment
1,2,3...
1.
Set the operation mode switch on the rear panel of the Unit to adjustment
mode.
2.
Turn ON the power to the PLC.
3.
Adjust the offset and gain.
4.
Turn OFF the power to the PLC.
5.
Change the setting of the operation mode switch on the rear panel of the
Unit back to normal mode.
Operation
1,2,3...
1.
Turn ON the power to the PLC.
2.
Ladder program
• Write set values by means of MOV(021) and XFER(070).
• Start and stop conversion output.
• Obtain error codes.
4-2-1
Procedure Examples
Setting the Analog Output Unit
1,2,3...
1.
Set the operation mode switch on the rear panel of the Unit. Refer to
for further details.
CS1W-DA041
CS-series CPU Unit
Unit No. 1
Analog output
OUT1: 1 to 5 V
OUT2: 1 to 5 V
OUT3: –10 to 10 V
OUT4: Not used
Ladder Prog
ra
m
Turn OFF SW1 for normal mode
Содержание CJ1W-AD041-V1