91
Components and Switch Settings
Section 3-3
Always turn OFF the power before setting the unit number. Use a flat-blade
screwdriver, being careful not to damage the slot in the screw. Be sure not to
leave the switch midway between settings.
Note
If two or more Special I/O Units are assigned the same unit number, a “UNIT
No. DPL ERR” error (in the Programming Console) will be generated (A40113
will turn ON) and the PLC will not operate.
3-3-3
Operation Mode Switch
The operation mode switch on the front panel of the Unit is used to set the
operation mode to either normal mode or adjustment mode (for adjusting off-
set and gain).
!Caution
Do not set the pins to any combination other than those shown in the above
table. Be sure to set pin 2 to OFF.
!Caution
Be sure to turn OFF the power to the PLC before installing or removing the
Unit.
Note
The operation mode can also be set using bits 00 to 07 of DM word m+18, in
addition to the hardware operation mode switch. The contents of DM word
m+18 are shown below
.
m = (unit number x 100)
Switch
setting
Unit
number
Special/O Unit Area
addresses
Special I/O Unit DM Area
addresses
0
Unit #0
CIO 2000 to CIO 2009
D20000 to D20099
1
Unit #1
CIO 2010 to CIO 2019
D20100 to D20199
2
Unit #2
CIO 2020 to CIO 2029
D20200 to D20299
3
Unit #3
CIO 2030 to CIO 2039
D20300 to D20399
4
Unit #4
CIO 2040 to CIO 2049
D20400 to D20499
5
Unit #5
CIO 2050 to CIO 2059
D20500 to D20599
6
Unit #6
CIO 2060 to CIO 2069
D20600 to D20699
7
Unit #7
CIO 2070 to CIO 2079
D20700 to D20799
8
Unit #8
CIO 2080 to CIO 2089
D20800 to D20899
9
Unit #9
CIO 2090 to CIO 2099
D20900 to D20999
10
Unit #10
CIO 2100 to CIO 2109
D21000 to D21099
~
~
~
~
n
Unit #n
CIO 2000 + (n x 10) to
CIO 2000 + (n x 10) + 9
(n x 100) to
(n x 100) + 99
~
~
~
~
95
Unit #95
CIO 2950 to CIO 2959
D29500 to D29599
MACH
No
.
10
1
10
0
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
Pin number
Mode
1
2
OFF
OFF
Normal mode
ON
OFF
Adjustment mode
O
N
12
MODE
Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
D (m+18)
Conversion time/resolution setting
00: Conversion time of 1 ms and resolution of 4,000
C1: Conversion time of 250
µ
s and resolution of 8,000
Operation mode setting
00: Normal mode
C1: Adjustment mode
Содержание CJ1W-AD041-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x TABLE OF CONTENTS...
Страница 15: ...xvi...
Страница 99: ...76 Handling Errors and Alarms Section 2 8...
Страница 191: ...168 Handling Errors and Alarms Section 4 8...
Страница 243: ...220 Handling Errors and Alarms Section 5 8...
Страница 381: ...358 Handling Errors and Alarms Section 7 10...
Страница 385: ...362 Dimensions Appendix A...
Страница 395: ...372 Sample Programs Appendix B...
Страница 396: ...373 Appendix C Data Memory Coding Sheets...
Страница 417: ...394 Data Memory Coding Sheets Appendix C...
Страница 425: ......