47
Exchanging Data with the CPU Unit
Section 2-5
CS1W-AD161
Note
1.
The Special I/O Unit Area words that are occupied by the Analog Input Unit
are set using the unit number switch on the front panel of the Unit. Refer to
for details on the method used to set the unit
number switch.
2.
If two or more Special I/O Units are assigned the same unit number, a
“UNIT No. DPL ERR” error (in the Programming Console) will be generat-
ed (A40113 will turn ON) and the PLC will not operate.
Allocations for Normal
Mode
For normal mode, set to OFF the operation mode switch on the rear panel of
the Unit as shown in the following diagram, or set bits 00 to 07 in DM word
m+18.
The allocation of words and bits in the CIO Area is shown in the following
table.
Special I/O Unit CIO Area
Allocated addresses
Normal mode
Unit #0
CIO 2000 to CIO 2019
Unit #1
CIO 2010 to CIO 2029
Unit #2
CIO 2020 to CIO 2039
CIO n
OUT refresh
Unit #3
CIO 2030 to CIO 2049
CIO n+1 to
Unit #4
CIO 2040 to CIO 2059
IN refresh
Unit #5
CIO 2050 to CIO 2069
CIO n+19
Unit #6
CIO 2060 to CIO 2079
Unit #7
CIO 2070 to CIO 2089
Adjustment mode
Unit #8
CIO 2080 to CIO 2099
Unit #9
CIO 2090 to CIO 2109
CIO n to
Unit #10
CIO 2100 to CIO 2119
CIO n+17
OUT refresh
CIO n+18 to
Unit #N
CIO 2000 + (n x 10)
to CIO 2000 +
(n x 10) + 19
IN refresh
CIO n+19
Unit #94
CIO 2940 to CIO 2959
Unit #95
n = 2000 + (unit number x 10)
to
to
to
to
I/O refresh
CS-series CPU Unit
CS1W-AD161
Analog Input Unit
Cannot be set.
At the I/O refresh
by the PLC, out-
puts (CPU to
Unit) and inputs
(Unit to CPU) are
refreshed in or-
der with every
cycle.
Operation data
Содержание CJ1W-AD041-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x TABLE OF CONTENTS...
Страница 15: ...xvi...
Страница 99: ...76 Handling Errors and Alarms Section 2 8...
Страница 191: ...168 Handling Errors and Alarms Section 4 8...
Страница 243: ...220 Handling Errors and Alarms Section 5 8...
Страница 381: ...358 Handling Errors and Alarms Section 7 10...
Страница 385: ...362 Dimensions Appendix A...
Страница 395: ...372 Sample Programs Appendix B...
Страница 396: ...373 Appendix C Data Memory Coding Sheets...
Страница 417: ...394 Data Memory Coding Sheets Appendix C...
Страница 425: ......