134
Operating Procedure
Section 4-2
• The following diagram shows the output range settings. Refer to
Output Settings and Conversions
for more details.
2.
Restart the CPU Unit.
Creating Ladder Programs
The setting address D00200 is stored in words (n + 1) to (n + 3) of the Special
I/O Unit Area (CIO 2011 to CIO 2013) as a signed binary value between 0000
to 0FA0 Hex.
15
14
13
12
11
10
09
08
07
06
05
01
00
04
03
02
0 0 0 0 0 0 0 0 0 0 0 0 1 0 1 0
Bit
m+1: DM20101
(000A Hex)
Output 1: 1 to 5 V. Set to 10.
Output 2: 1 to 5 V. Set to 10.
Output 3: –10 to 10 V. Set to 00.
Output 4: Not used. Set to 00 (disabled).
Power turned ON again
(or Special I/O Unit Restart Bit is turned ON)