328
Analog Output Functions and Operating Procedures
Section 7-7
gramming Device to set the D(m+1) bits in the DM Area shown in the following
diagram.
Note
1.
For the DM word addresses, m = (unit number x 100).
2.
After making the DM settings from a Programming Device, it will be neces-
sary to either turn the power to the PLC OFF and ON, or turn ON the Spe-
cial I/O Unit Restart Bit to transfer the contents of the DM settings to the
Special I/O Unit.
Voltage/Current Range
Setting
When “1 to 5 V, 4 to 20 mA” is selected for the output signal range, either the
“1 to 5 V” or “4 to 20 mA” range can then be selected by means of the
D(m+35) setting. Adjusting the factory-set voltage and current can improve
the accuracy of current output specifications.
Writing Set Values
Analog output set values are written to CIO words (n+1) and (n+2).
For the CIO word addresses, n = CIO 2000 + (unit number x 10).
Use MOV(021) or XFER(070) to write values in the user program.
Example 1
In this example, the set value from only one input is read. (The unit number is
0.)
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Bit
D(m + 1)
Output 2
Output 1
00:
−
10 to 10 V
01: 0 to 10 V
10: 1 to 5 V
11: 0 to 5 V
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Bit
D(m+35)
Output 2
Output 1
0: Voltage: 1 V to 5 V
1: Current 4 mA to 20 mA
Word
Function
Stored value
n+1
Output 1 set value
16-bit binary data
n+2
Output 2 set value
MOV (021)
D00001
2001
Input condition
The set value stored in D 00001
is written to CIO word 2001 (out-
put number 1).
Содержание CJ1W-AD041-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x TABLE OF CONTENTS...
Страница 15: ...xvi...
Страница 99: ...76 Handling Errors and Alarms Section 2 8...
Страница 191: ...168 Handling Errors and Alarms Section 4 8...
Страница 243: ...220 Handling Errors and Alarms Section 5 8...
Страница 381: ...358 Handling Errors and Alarms Section 7 10...
Страница 385: ...362 Dimensions Appendix A...
Страница 395: ...372 Sample Programs Appendix B...
Страница 396: ...373 Appendix C Data Memory Coding Sheets...
Страница 417: ...394 Data Memory Coding Sheets Appendix C...
Страница 425: ......