389
Data Memory Coding Sheets
Appendix C
Note
m=20000+ unit number x 100 is allocated as the DM number.
DM word
Setting contents
15
8
7
0
m
m+1
m+2
m+3
m+4
m+5
m+6
m+7
m+8
m+9
m+10 to m+17
m+18
m+19
m+20
m+21
m+22
m+23
m+24
m+25
m+26
m+27
m+28
m+29
m+30
m+31
m+32
m+33
m+34
---
---
---
---
---
---
---
---
---
Output use designation
Output signal range settings
Output 1: Output status
when conversion stopped
Output 2: Output status
when conversion stopped
Output 3: Output status
when conversion stopped
Output 4: Output status
when conversion stopped
Output 5: Output status
when conversion stopped
Output 6: Output status
when conversion stopped
Output 7: Output status
when conversion stopped
Output 8: Output status
when conversion stopped
---
Conversion time/
resolution setting
Operation mode setting
Output 1 scaling lower limit
Output 1 scaling upper limit
Output 2 scaling lower limit
Output 2 scaling upper limit
Output 3 scaling lower limit
Output 3 scaling upper limit
Output 4 scaling lower limit
Output 4 scaling upper limit
Output 5 scaling lower limit
Output 5 scaling upper limit
Output 6 scaling lower limit
Output 6 scaling upper limit
Output 7 scaling lower limit
Output 7 scaling upper limit
Output 8 scaling lower limit
Output 8 scaling upper limit
Use Designation
07 06 05 04 03 02 01 00
Output 6
Output 5
Output 2
Output 1
0: Do not use
1: Use
Output 8
Output 7
Output 4
Output 3
Output Signal Range Settings
(Not valid for the CJ1W-DA08C.)
07 06 05 04 03 02 01 00
Output 2
Output 1
Output 4
Output 3
15 14 13 12 11 10 09 08
Output 6
Output 5
Output 8
Output 7
00:
−
10 to 10 V
01: 0 to 10 V
10: 1 to 5 V
11: 0 to 5 V
Output Status when Conversion Stopped
07 04 03 00
16
1
16
0
00: CLR (0 or minimum value for each range output)
01: HOLD (Hold prior output value.)
02: MAX (Output maximum value of range.)
Conversion Time and Resolution Setting
Operation Mode
15 12 11 08
07 04 03 00
00: Conversion time = 1 ms, resolution = 4,000
C1: Conversion time = 250
µ
s, resolution = 8,000
00: Normal mode
C1: Adjustment mode
Содержание CJ1W-AD041-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x TABLE OF CONTENTS...
Страница 15: ...xvi...
Страница 99: ...76 Handling Errors and Alarms Section 2 8...
Страница 191: ...168 Handling Errors and Alarms Section 4 8...
Страница 243: ...220 Handling Errors and Alarms Section 5 8...
Страница 381: ...358 Handling Errors and Alarms Section 7 10...
Страница 385: ...362 Dimensions Appendix A...
Страница 395: ...372 Sample Programs Appendix B...
Страница 396: ...373 Appendix C Data Memory Coding Sheets...
Страница 417: ...394 Data Memory Coding Sheets Appendix C...
Страница 425: ......