135
Operating Procedure
Section 4-2
The following table shows the addresses used for analog output.
Note
1.
The addresses are set according to the unit number of the Special I/O Unit.
Refer to
for further details.
2.
Set as required.
Output number
Output signal
range
Output setting
address
(n = CIO 2010)
See note 1.
Original
conversion
address
1
1 to 5 V
(n+1) = CIO 2011
D00200
2
0 to 10 V
(n+2) = CIO 2012
D00201
3
–10 to 10 V
(n+3) = CIO 2013
D00202
4
Not used.
---
---
D00200 is set in word CIO 2011.
D00201 is set in word CIO 2012.
D00202 is set in word CIO 2013.
To start analog output, turn ON the
Conversion Enable Bits 201000 to
201002 (bits 00 to 03 of word
CIO 2010).
The data in words CIO 2011 and
2012 will be output as 1 to 5 V, and
CIO the data in CIO 2013 will be
output as –10 to 10 V.
MOV (021)
D00200
2011
MOV (021)
D00201
2012
Execution condition
MOV (021)
D00202
2013
SET
201000
SET
201002
SET
201001
Execution condition
for details.
Содержание CJ1W-AD041-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x TABLE OF CONTENTS...
Страница 15: ...xvi...
Страница 99: ...76 Handling Errors and Alarms Section 2 8...
Страница 191: ...168 Handling Errors and Alarms Section 4 8...
Страница 243: ...220 Handling Errors and Alarms Section 5 8...
Страница 381: ...358 Handling Errors and Alarms Section 7 10...
Страница 385: ...362 Dimensions Appendix A...
Страница 395: ...372 Sample Programs Appendix B...
Страница 396: ...373 Appendix C Data Memory Coding Sheets...
Страница 417: ...394 Data Memory Coding Sheets Appendix C...
Страница 425: ......