64
Adjusting Offset and Gain
Section 2-7
Wiring for Voltage Input
Wiring for Current Input
When using current input, short-circuit the input (+) terminal and the current
mode terminal.
3.
Input the voltage or current so that the conversion value becomes 0000.
The following table shows the offset adjustment voltages and currents to
be input according to the input signal range.
Input signal range
Input range
Word (n+8) monitoring
value
0 to 10 V
–0.5 to 0.5 V
FF38 to 00C8 (4,000 res-
olution)
FE70 to 0190 (8,000 res-
olution)
–10 to 10 V
–1.0 to 1.0 V
1 to 5 V
0.8 to 1.2 V
0 to 5 V
–0.25 to 0.25 V
4 to 20 mA
3.2 to 4.8 mA
A1
A2
A3
+
–
Voltage input
Input 1
CS1W-AD041-V1/081-V1
Voltage n
+
−
Shield
Input n+
Current mode n
Input n
−
AG
CS1W-AD161
A1
A2
A3
+
–
Current input
Input 1
For current input, check that the voltage/
current switch is ON.
CS1W-AD041-V1/081-V1
Current input n
+
−
Shield
Input n+
Current mode n
Input n
−
AG
CS1W-AD161
Содержание CJ1W-AD041-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x TABLE OF CONTENTS...
Страница 15: ...xvi...
Страница 99: ...76 Handling Errors and Alarms Section 2 8...
Страница 191: ...168 Handling Errors and Alarms Section 4 8...
Страница 243: ...220 Handling Errors and Alarms Section 5 8...
Страница 381: ...358 Handling Errors and Alarms Section 7 10...
Страница 385: ...362 Dimensions Appendix A...
Страница 395: ...372 Sample Programs Appendix B...
Страница 396: ...373 Appendix C Data Memory Coding Sheets...
Страница 417: ...394 Data Memory Coding Sheets Appendix C...
Страница 425: ......