179
Operating Procedure
Section 5-2
• The following diagram shows the output settings used. Refer to
Output Settings and Conversions
for more details.
• The following diagram shows the output range settings. Refer to
Output Settings and Conversions
for more details.
Note
The output range setting is not required for the CJ1W-DA08C.
• The following diagram shows the conversion time/resolution setting for
the DA08V. (Refer to
5-6-2 Conversion Time/Resolution Setting
2.
Turn OFF the external power supply.
3.
Restart the CPU Unit.
4.
Turn ON the external power supply.
15
14 13
12 11 10
09 08 07
06 05
01 00
04 03
02
0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1
Bit
Not used
Output 4
Output 3
Output 2
Output 1
Used
m: DM20100
(0007 Hex)
15
14 13
12 11 10
09 08 07
06 05
01 00
04 03
02
0 0 0 0 0 0 0 0 0 0 0 0 1 0 1 0
Bit
m+1: DM20101
(000A Hex)
Output 1: 1 to 5 V. Set to 10.
Output 2: 1 to 5 V. Set to 10.
Output 3: –10 to 10 V. Set to 00.
Output 4: Not used. Set to 00 (disabled).
15
14
13
12
11
10
09
08
07
06
05
01
00
04
03
02
0 0 0 0 0 0 0 0
Bit
m+18: D20118
(0000 Hex)
Conversion Time/Resolution Setting
0000: 1-ms conversion time, 4,000 resolution
C100: 250-
µ
s conversion time, 8,000 resolution
Содержание CJ1W-AD041-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x TABLE OF CONTENTS...
Страница 15: ...xvi...
Страница 99: ...76 Handling Errors and Alarms Section 2 8...
Страница 191: ...168 Handling Errors and Alarms Section 4 8...
Страница 243: ...220 Handling Errors and Alarms Section 5 8...
Страница 381: ...358 Handling Errors and Alarms Section 7 10...
Страница 385: ...362 Dimensions Appendix A...
Страница 395: ...372 Sample Programs Appendix B...
Страница 396: ...373 Appendix C Data Memory Coding Sheets...
Страница 417: ...394 Data Memory Coding Sheets Appendix C...
Страница 425: ......