1.
If two or more Special I/O Units are assigned the same unit number, a
“UNIT No. DPL ERR” error (in the Programming Console) will be generat-
ed (A40113 will turn ON) and the PLC will not operate.
2.
A single CS1W-AD161 is allocated CIO Area words and DM Area words
for two Units. Be sure to set a unit number so that the CS1W-AD161 is not
allocated words in the CIO Area and DM Area that are already allocated to
other Special I/O Units. For example, if the CS1W-AD161 is set to unit
number n, another Special I/O Unit cannot be set with unit number n+1.
The highest unit number that can be set for a CS1W-AD161 is unit number
94.
2-3-3
Operation Mode Switch
The operation mode switch on the back panel of the Unit is used to set the
operation mode to either normal mode or adjustment mode (for adjusting off-
set and gain).
Note
1.
The operation mode can be set in the DM Area as an alternative to using
the operation mode switch.
2.
Set the operation mode in DM word m+18 for CS1W-AD041-V1 and
CS1W-AD081-V1, and in DM word m+19 for CS1W-AD161.
CS1W-AD041-V1/AD081-V1
m = (unit number x 100)
CS1W-AD161
m = (unit number x 100)
Pin number
Mode
1
2
OFF
OFF
Normal mode
ON
OFF
Adjustment mode
Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
D (m+18)
Conversion time/resolution setting
Operation mode setting
00: Normal mode
C1: Adjustment mode
Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
D (m+19)
Conversion time/resolution setting
Operation mode setting
00: Normal mode
C1: Adjustment mode
Содержание CJ1W-AD041-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x TABLE OF CONTENTS...
Страница 15: ...xvi...
Страница 99: ...76 Handling Errors and Alarms Section 2 8...
Страница 191: ...168 Handling Errors and Alarms Section 4 8...
Страница 243: ...220 Handling Errors and Alarms Section 5 8...
Страница 381: ...358 Handling Errors and Alarms Section 7 10...
Страница 385: ...362 Dimensions Appendix A...
Страница 395: ...372 Sample Programs Appendix B...
Страница 396: ...373 Appendix C Data Memory Coding Sheets...
Страница 417: ...394 Data Memory Coding Sheets Appendix C...
Страница 425: ......