![Omron CJ Series Скачать руководство пользователя страница 160](http://html1.mh-extra.com/html/omron/cj-series/cj-series_operation-manual_742334160.webp)
3-1 Routing Table Overview
3-1-6 Operating Procedures Prior to Routing Table Transfer
3-7
Method 2: Transferring to a PLC in the Same Network as the Directly
Connected PLC (FINS Local Routing Table Only)
When a PLC is connected directly by serial communications, the routing tables can be
transferred to each PLC in the same network as the directly connected PLC. (See
notes 1 and 2.)
The routing tables cannot be transferred to another network level.
Note 1: Use
CX-Integrator version 2.1 or higher.
Note 2: Use one of the following PLC models as the PLC directly connected by serial
communications.
•
A CS/CJ-series CPU Unit with unit version 4.0 or later
Computer (CX-Integrator)
CS/CJ-series
PLC1 (See note.)
Connect online with
network address = 0, and
node address = 0.
CS/CJ-series PLC2
Can be transferred to other
PLCs in the network.
Note: Can be transferred even if PLC1
’
s local network table hasn
’
t been set.
Peripheral port
or
RS-232C port
(or USB port)
Routing
tables
CS/CJ-series PLC3
Direct serial
connection
Routing
tables
Note
When connecting online through Ethernet, the FINS network routing table cannot be
set or transferred if there is even one node in the network that does not automatically
generate an Ethernet IP address from the FINS node address. Be sure that all of the
nodes will automatically generate IP addresses when using Ethernet.
3-1-6
Operating Procedures Prior to Routing Table Transfer
This section describes the operating procedures necessary to create the routing
tables for the first time up to the point where the files are transferred to the PLCs.
Note
When constructing the network, set FINS local routing tables in all nodes (CPU Units)
that will participate in the network.
Содержание CJ Series
Страница 2: ......
Страница 3: ...CXONE AL C V3 CXONE AL D V3 CX Integrator Ver 2 3 Operation Manual Revised February 2009 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 18: ...xviii ...
Страница 154: ...Communications Section 3 Routing Tables This section describes how to set the routing tables ...
Страница 189: ...3 3 Maintenance after Network Configuration 3 3 2 Editing the FINS Local Network Tables 3 36 ...
Страница 244: ...Communications Section 5 Ethernet This section describes the operations specific to Ethernet ...
Страница 249: ...5 2 Ping Test 5 2 2 Procedure 5 6 ...
Страница 353: ...7 8 Other CompoNet Functions 7 8 2 Installing Expansion Modules 7 32 ...
Страница 354: ...Communications Section 8 CompoWay F This section explains the settings and operations specific to the CompoWay F system ...
Страница 368: ...Communications Section 9 NT Links This section explains the settings and operations specific to the NT Link system ...
Страница 404: ...Appendices ...
Страница 407: ...A 1 CPS File Management A 1 1 Description of CPS Files A 4 ...
Страница 413: ......
Страница 414: ......
Страница 415: ......