3 Network Startup
3 - 16
CompoNet Communications Unit User’s Manual (I582-E1)
*1 Node addresses are distributed because the area occupied by a 32-point Output Unit, which occupies more
than one node address, is not overlapping with the area occupied by an 8-point Input Slave.
Allocation to the Special I/O Unit allocation relay area can be performed without CX-Integrator.
Follow the steps below.
1
Power on the inverter(s) first and configure the following settings according to
• Set the node address. According to
rotary switches or CompoNet node address (P190).
• Set the type of Remote I/O. Set inverter parameter P046 (Assembly Instance No.) that suits
your application.
Precautions for Correct Use
Precautions for Correct Use
• Be sure to set the type of Remote I/O at this point. No. of occupied words by the CompoNet
Communications Unit varies with the Remote I/O type. Unless the Remote I/O type is set
correctly, automatic network configuration cannot be completed successfully.
• To connect additional CompoNet Slaves, set the node addresses for them simultaneously
at this point.
2
Set the Special I/O Unit number (Machine No.) and communications mode number (MODE)
rotary switches on the Master Unit. Cycle the power supply of the inverter. Then, power on
all network components (Master Unit, other Slaves, communications power supply, etc.).
3
Once the inverter(s) and all network components are powered on, check that the Com-
poNet Communications Unit's LED indicators indicate normal operation.
If everything is correctly configured, both the MS (Module Status) LED and the NS (Network Sta-
tus) LED are lit green.
If the LED indicators indicate a different pattern, please refer to
page 6-1 to take corrective action.
Allocation
Address
Output Allocation Relay Area
Input Allocation Relay Area
Allocation
Relay
15 to 0
Allocation
Relay
15 to 0
00
CIO 2000
32-point Output Unit
[Node Address 0]
CIO 2016
– (Not allocatable)
01
CIO 2001
CIO 2017
–
(Not allocatable)
8-point Input Unit
*1
[Node Address 1]
02
CIO 2002
This CompoNet Communica-
tions Unit [Node address 2]
Extended Speed I/O setting:
Occupies 2 output words
CIO 2018
This CompoNet Communications
Unit [Node address 2]
Extended Speed I/O setting: Occu-
pies 2 input words
03
CIO 2003
CIO 2019
04
CIO 2004
This CompoNet Communica-
tions Unit [Node address 4]
Extended Control I/O setting:
Occupies 4 output words
CIO 2020
This CompoNet Communications
Unit [Node address 4]
Extended Control I/O setting: Occu-
pies 4 input words
05
CIO 2005
CIO 2021
06
CIO 2006
CIO 2022
07
CIO 2007
CIO 2023
08
CIO 2008
–
(Not allocatable)
CIO 2024
32-point Input Unit
[Node Address 8]
*1
···
···
···
···
···
3-2-3
Allocation to Special I/O Unit Allocation Relay Area
(Communications Mode No. 0 to 3)
Содержание 3G3AX-MX2-CRT-E
Страница 58: ...2 CompoNet Communications Unit Mounting and Wiring 2 16 CompoNet Communications Unit User s Manual I582 E1...
Страница 94: ...3 Network Startup 3 36 CompoNet Communications Unit User s Manual I582 E1...
Страница 118: ...4 Remote I O 4 24 CompoNet Communications Unit User s Manual I582 E1...
Страница 134: ...5 Message Communications 5 16 CompoNet Communications Unit User s Manual I582 E1...
Страница 167: ...I 1 I CompoNet Communications Unit User s Manual I582 E1 Index...
Страница 171: ......