Drive Status Detail
0: Stopping
1: Running
2: Jogging
3: Free running
4: Direct current DC braking
5: Restart (Retry)/Error detection (Deceleration stop)
7: Restart (Retry) in process
8: Waiting for restart (retry)
10: Fault/Trip
11: Undervoltage condition
Rotation Speed Monitor
If parameter P049 (Number of Poles for Rotation Speed Setting) is set appropri-
ately, the rotational speed unit is [min
-1
].
If parameter P049 (Number of Poles for Rotation Speed Setting) is set to 0, the
frequency is monitored in units of [0.01 Hz].
Output Current Monitor
Unit: [0.1 A]
Trip Cause
Displays direct trip cause. Decimal values 1 to 99 correspond to trips E01 to
E99.
Name
Description