3 - 27
3 Network Startup
CompoNet Communications Unit User’s Manual (I582-E1)
3-3 Editing
Par
a
meter
s
in Param
eter Dialo
g
with
EDS
F
ile
3
3-
3-2 R
estr
ictions
of Edit D
evice Parameter
s F
unction
with
E
D
S File
*1 The process will be terminated abnormally if the same set value exists in Multi-function input selection 1 to 8.
The process will also be terminated abnormally if, when setting values in the order of Multi-function input selec-
tion 1 to 8, the value already set for a latter parameter is set for a preceding parameter.
*2 The process will be terminated if the frequency set for F001, A020, A220, or A021 to A035 is within the fre-
quency range set for Jump frequency.
Restrictions between Parameters
Multi-function Input Selection 1 to 8 (C001 to C008)
=
Multi-function Input Selection 1 to 8 (C001 to
C008)
*1
1st Frequency Upper Limit (A061)
>
1st Maximum Frequency (A004)
1st Frequency Lower Limit (A062)
>
1st Maximum Frequency (A004)
Output Frequency Setting (F001),
1st Multi-step Speed Reference 0 (A020)
>
1st Maximum Frequency (A004)
Output Frequency Setting (F001),
1st Multi-step Speed Reference 0 (A020)
>
1st Frequency Upper Limit (A061)
1st Frequency Lower Limit (A062)
>
Output Frequency Setting (F001),
1st Multi-step Speed Reference 0 (A020)
Starting Frequency (B082)
>
1st Frequency Upper Limit (A061)
Starting Frequency (B082)
>
1st Frequency Lower Limit (A062)
Starting Frequency (B082)
>
Output Frequency Setting (F001),
1st Multi-step Speed Reference 0 (A020)
Starting Frequency (B082)
>
Jogging Frequency (A038)
Output Frequency Setting (F001),
1st Multi-step Speed Reference 0 (A020)
=
Jump Frequency
*1
(A063/A065/A067 ± A064/A066/A068)
Multi-step Speed Reference 1 to 15 (A021 to A035)
=
Free V/f Frequency 7 (B112)
>
1st Frequency Upper Limit (A061)
Free V/f Frequency 7 (B112)
>
1st Frequency Lower Limit (A062)
Free V/f Frequency 7 (B112)
>
Output Frequency Setting (F001),
1st Multi-step Speed Reference 0 (A020)
2nd Frequency Upper Limit (A261)
>
2nd Maximum Frequency (A204)
2nd Frequency Lower Limit (A262)
>
2nd Maximum Frequency (A204)
Output Frequency Setting (F001),
2nd Multi-step Speed Reference 0 (A220)
>
2nd Maximum Frequency (A204)
Output Frequency Setting (F001),
2nd Multi-step Speed Reference 0 (A220)
>
2nd Frequency Upper Limit (A261)
2nd Frequency Lower Limit (A262)
>
Output Frequency Setting (F001),
2nd Multi-step Speed Reference 0 (A220)
Starting Frequency (B082)
>
2nd Frequency Upper Limit (A261)
Starting Frequency (B082)
>
2nd Frequency Lower Limit (A262)
Starting Frequency (B082)
>
Output Frequency Setting (F001),
2nd Multi-step Speed Reference 0 (A220)
Output Frequency Setting (F001),
2nd Multi-step Speed Reference 0 (A220)
=
Jump Frequency
*2
(A063/a065/a067 ± A064/a066/a068)
Free V/f Frequency 7 (B112)
>
2nd Frequency Upper Limit (A261)
Free V/f Frequency 7 (B112)
>
2nd Frequency Lower Limit (A262)
Free V/f Frequency 7 (B112)
>
Output Frequency Setting (F001),
2nd Multi-step Speed Reference 0 (A220)
Содержание 3G3AX-MX2-CRT-E
Страница 58: ...2 CompoNet Communications Unit Mounting and Wiring 2 16 CompoNet Communications Unit User s Manual I582 E1...
Страница 94: ...3 Network Startup 3 36 CompoNet Communications Unit User s Manual I582 E1...
Страница 118: ...4 Remote I O 4 24 CompoNet Communications Unit User s Manual I582 E1...
Страница 134: ...5 Message Communications 5 16 CompoNet Communications Unit User s Manual I582 E1...
Страница 167: ...I 1 I CompoNet Communications Unit User s Manual I582 E1 Index...
Страница 171: ......