6 Troubleshooting
6 - 12
CompoNet Communications Unit User’s Manual (I582-E1)
6-5
Special I/O Errors
If a problem is found in the output data of Special I/O, the inverter returns an error code to the input data
without executing the request.
Determine whether or not an error occurred by the most significant bit (word address n, bit 7) of the
Function Code in the input data.
In case of an error, the Function Code in the input data has a value of the output data added with
80 hex.
The table below shows the error code and corrective action for each Special I/O error.
*1 UV: During undervoltage
Error Code
Name
Description
Corrective Action
01 hex
Function Code
Error
A code other than 03/10/43 or 50 hex
is set as Function Code.
Check and correct Function Code.
02 hex
Register No.
Error
Specified Register No. does not exist.
Check and correct Register No.
04 hex
Slave Device
Error
Option inverter communications error.
(Internal communications error
occurred between CompoNet Commu-
nications Unit and inverter)
Check if CompoNet Communica-
tions Unit is mounted properly (if
connector is sufficiently inserted).
If problem persists, replace Compo-
Net Communications Unit.
21 hex
Data Setting Error
Upper or lower limit of write data set-
ting range is exceeded.
Check and correct data size so data
is within data setting range.
22 hex
Write Mode Error
Inverter mode is incorrect.
• Changing unchangeable register
during operation.
• ENTER command was issued dur-
ing operation (UV
*1
).
• Writing to register in trip (UV
*1
)
state.
• Writing to register in soft lock mode.
• Changing an unchangeable
input/output terminal.
• Changing contact type of terminal to
which RS (Reset) is allocated.
• Writing to a register when auto-tun-
ing is enabled.
• Writing to a lock-enabled register
during password setting.
• Write after stopping inverter oper-
ation.
• Write after clearing UV error.
• Write after releasing soft lock.
• Correct after checking if terminal
is changeable.
• Write after completing auto-tuning.
• Write after canceling password
setting.
23 hex
Register Size
Error
Reading/Writing 2-byte data from/to a
4-byte register or 4-byte data from/to a
2-byte register.
Check and correct data size prop-
erly.
Содержание 3G3AX-MX2-CRT-E
Страница 58: ...2 CompoNet Communications Unit Mounting and Wiring 2 16 CompoNet Communications Unit User s Manual I582 E1...
Страница 94: ...3 Network Startup 3 36 CompoNet Communications Unit User s Manual I582 E1...