Appendices
A - 12
CompoNet Communications Unit User’s Manual (I582-E1)
Table A-20 Control Supervisor Object - Object Details
Additional Information
The comparison between the inverter Error/Trip codes and the CIP Fault/Warning codes is
shown in Table A-20.
A-2-2
Control Supervisor Object (Class 29 hex)
Supported Service Codes
Table A-19 Control Supervisor Object - Supported Service Codes
Service Code No. (hex)
Service Description
0E
Reads Attribute data.
10
Writes Attribute data.
Object Details
Instance
(hex)
Attribute
(hex)
Name
Description
Setting
Range
Default
Read Write
Size
01
03
Forward/
Stop
0: Stop
1: Forward
----
0
Yes
Yes
BOOL
04
Reverse/
Stop
0: Stop
1: Reverse
----
0
Yes
Yes
BOOL
05
Net Control
0: Follow the setting of param-
eter A002.
1: CompoNet reference
----
0
Yes
Yes
BOOL
06
State
Drive status
----
----
Yes
No
UINT
07
During For-
ward Run
0: Stop
1: During forward run
----
----
Yes
No
BOOL
08
During
Reverse
Run
0: Stop
1: During reverse run
----
----
Yes
No
BOOL
09
Inverter
Ready
0: Not ready
1: Ready
----
----
Yes
No
UINT
0A
Fault
0: Normal
1: Fault
----
----
Yes
No
BOOL
0B
Alarm
0: Normal
1: Alarm
----
----
Yes
No
BOOL
0C
Fault Reset
Resets the Fault/Trip state of
the inverter when 1 is written.
----
0
Yes
Yes
BOOL
0D
Fault Code
Fault/Trip state code
----
----
Yes
No
UINT
Содержание 3G3AX-MX2-CRT-E
Страница 58: ...2 CompoNet Communications Unit Mounting and Wiring 2 16 CompoNet Communications Unit User s Manual I582 E1...
Страница 94: ...3 Network Startup 3 36 CompoNet Communications Unit User s Manual I582 E1...
Страница 118: ...4 Remote I O 4 24 CompoNet Communications Unit User s Manual I582 E1...
Страница 134: ...5 Message Communications 5 16 CompoNet Communications Unit User s Manual I582 E1...
Страница 167: ...I 1 I CompoNet Communications Unit User s Manual I582 E1 Index...
Страница 171: ......