10
If the delivery pressures are too high, a delivery
pressure limiter (e.g. supplementary air device in the
chimney) must be fitted. It is purposeful to re-
determine the delivery pressure when starting up the
stove. The measurement should be taken when the
chimney is warm.
Combustion air supply
Ensure an adequate combustion air supply.
Important:
The combustion air inlet and convection
air openings may not be closed or covered!
Note:
Extractor hoods or ventilation systems operat-
ed together with the fireplace in the same air com-
partment space can cause problems. Permissibility of
the joint operation must be clarified before the instal-
lation takes place.
Installing the stove
The floor on which the stove is installed must be
even and horizontal. The stove may only be installed
on an adequate load-bearing floor. The stove can be
stood on a metal floor sheet or glass sheet to protect
the flooring. If the flooring or carpet is inflammable, a
stable, heatproof base must be used. This must ex-
tend 50 cm to the front and 30 cm to each side be-
yond the edge of the combustion chamber opening.
Assembly sequence
•
The Ø 150 stovepipe connection can be installed
at the top or rear.
•
The stove is supplied ready for connection from
above. If you
wish
to connect it at the rear, the
following steps must be carried out to make the
necessary modifications:
-
Unscrew the cover at the back
-
Unscrew the sealing cap at the back. Use a
screwdriver to secure the screws through the
connection pipe from turning too.
-
Unscrew the connection pipe through the rear
hole.
-
After
successfully
changing
the
sealing
cap/connection pipe close off the hole in the top
cover with the enclosed insertable cap.
•
Decide where the stove is to be installed. There
must be no objects made of combustible materi-
als within a distance of 80 cm of the
stove’s
ra-
diation area, measured from the combustion
chamber’s inspection glass, nor may any be
placed within this area subsequently.
Minimum distance from combustible or load-
bearing walls:
Lateral and rear: 15 cm
•
Install the pipe lining (provided on site) in the
chimney.The connection height can be individual-
ly specified for a top stovepipe connection, how-
ever should not exceed 1.5 m from the connector
sleeve. For the rear stovepipe connection heights
please refer the “Technical Data“ table. No com-
bustible material is permitted within a radius of
20cm around the stove pipe.
•
Place the stovepipe (provided on site) on the
Ø160/Ø150mm transition piece of the stove.
•
Push the stove onto its planned position and
orient it so that the stovepipe fits into the pipe lin-
ing.
The stovepipe connections must be airtight. The
stovepipe must not protrude into the chimney.
Operation
Permissible fuels
The following fuels are approved:
•
Natural shopped wood in the form of billet wood
Maximum length:
33 cm
Circumference:
approx. 30 cm
•
Wood briquettes to DIN 51731
Size class HP 2
Maximum length: 20 cm
•
Brown coal briquette
Billet wood
reaches a moisture content of 10 to 15
% after being stored outdoors for 2 to 3 years (only
covered at the top) and is then ideally suited for heat-
ing.
Freshly cut wood
has a very high moisture content
and so burns badly. Apart from the very low calorific
value it is also harmful for the environment. The in-
creased condensate and tar formation can lead to
fireplace and chimney sooting.
You will only achieve optimum combustion and heat
in an environmentally friendly way with these fuels.
Adding the fuel in small quantities avoids unneces-
sary emissions. Clean burning can be identified by
the fact that the firebrick becomes a light colour.
According to the (German) Federal Immissions
Control Act, it is forbidden e.g. to burn the follow-
ing fuels in stoves:
•
Moist wood or wood treated with wood pre-
servatives
•
Sawdust, chippings, grinding dust
•
Bark and chipboard waste
•
Slack coal
•
Other wastes
•
Paper and cardboard (except for igniting)
•
Straw