Moving Your System
IF YOUR SYSTEM NEEDS TO BE MOVED FROM ITS PREVIOUSLY INSTALLED LOCATION FOR
ANY REASON, USE THE FOLLOW-ING PROCEDURE TO SECURE YOUR SYSTEM PRIOR TO
MOVING.
STEP 1.
Pump all Bulk Tanks empty.
STEP 2.
Depressurize the system by opening each faucet without the pumps running.
STEP 3.
Lock out the main power supply (Electric or Air supplies).
STEP 4.
Close the Fire Safety Valves on the bottom of all tanks
. Illustrated on Page #29.
STEP 5.
Flush out the spill transport pallet (bottom of the pods) with hot water and cleaner/degreasing fluid.
STEP 6.
Disconnect the following for each tank assembly:
a.
Power cord from wall outlet.
b.
Tank level gauge and desiccant breather from any upper tanks.
c.
Place the hoses and cords in the spill pan at the bottom of the Pod.
STEP
7.
Disconnect hoses on Spill Containment if Connector Kit is used (Page #14)
STEP 8.
Repeat all steps until each pod is isolated similar to how it was delivered initially.
STEP 9.
Using a hand pallet truck, position the Tank Pod (Pod-1) into its new service position, ensuring that there is at least
18" of free clear space at therear and each end of the system.
STEP 10.
Disconnect hoses on Spill Containment if Connector Kit is used (Page #14)
WARNING!
OilSafe DOES NOT recommend changing the type of fluid dispensed by a pump. Each system is custom-
built to customer specifications including the type of fluid stored. Contact your supplier if your fluid storage
needs change to remove the possibility of cross-contamination and incompatibility of system materials or
components with a new fluid.
Also be aware of any change in ambient room temperature in the new location. Ambient room temperature
should not be less than 60°F (15°C).