69
Inverter swimming pool heat pump
GB
The system values can be checked with the remote control. Procede as follows:
Step 1: Hold the arrow button until you enter the mode for confi rming the settings.
Step 2: Press the arrow buttons and to check the status values.
Step 3: Press
to return to the main screen.
Chart of status values
Status values
4.12
25
4.11 Status values
The status values can be checked via the remote control by following these steps.
Step 1:
Keep pressing
until you enter the settings verification mode.
Step 2:
Press
and
to check the status values.
Step 3:
Press
to return to the main screen.
Status values table
Code
Description
A01
Water inlet temperature (-30~150°C)
A02
Water outlet temperature (-30~150°C)
A03
Ambient temperature (-30~150°C)
A04
Discharge gaz temperature (0~150°C)
A05
Suction gaz temperature (-30~150°C)
A06
Outside coil temperature (-30~150°C)
A07
Inside coil temperature (-30~150°C)
A08
The openness of the expansion valve
A09
Reserved
A10
Compressor current (A)
A11
PCB temperature (°C)
A12
Fan motor current (A)
A13
Compressor real frequency (Hz)
A14
Main PCB current (A)
A15
Fan motor speed (RPS)
25
4.11 Status values
The status values can be checked via the remote control by following these steps.
Step 1:
Keep pressing
until you enter the settings verification mode.
Step 2:
Press
and
to check the status values.
Step 3:
Press
to return to the main screen.
Status values table
Code
Description
A01
Water inlet temperature (-30~150°C)
A02
Water outlet temperature (-30~150°C)
A03
Ambient temperature (-30~150°C)
A04
Discharge gaz temperature (0~150°C)
A05
Suction gaz temperature (-30~150°C)
A06
Outside coil temperature (-30~150°C)
A07
Inside coil temperature (-30~150°C)
A08
The openness of the expansion valve
A09
Reserved
A10
Compressor current (A)
A11
PCB temperature (°C)
A12
Fan motor current (A)
A13
Compressor real frequency (Hz)
A14
Main PCB current (A)
A15
Fan motor speed (RPS)
25
4.11 Status values
The status values can be checked via the remote control by following these steps.
Step 1:
Keep pressing
until you enter the settings verification mode.
Step 2:
Press
and
to check the status values.
Step 3:
Press
to return to the main screen.
Status values table
Code
Description
A01
Water inlet temperature (-30~150°C)
A02
Water outlet temperature (-30~150°C)
A03
Ambient temperature (-30~150°C)
A04
Discharge gaz temperature (0~150°C)
A05
Suction gaz temperature (-30~150°C)
A06
Outside coil temperature (-30~150°C)
A07
Inside coil temperature (-30~150°C)
A08
The openness of the expansion valve
A09
Reserved
A10
Compressor current (A)
A11
PCB temperature (°C)
A12
Fan motor current (A)
A13
Compressor real frequency (Hz)
A14
Main PCB current (A)
A15
Fan motor speed (RPS)
Step 1
Step 3
Step 2
Code
Description
A01
Water inlet temperature
A02
Water outlet temperature
A03
Ambient air temperature
A04
Discharge temperature
A05
Suction gas temperature
A06
Outer coil temperature
A07
Inner coil temperature
A08
Expansion valve opening
A09
Reserved
A10
Compressor current (A)
A11
PCB temperature (°C)
A12
Fan motor current (A)
A13
Actual compressor frequency (Hz)
A14
PCB current (A)
A15
Fan motor speed (R/sec)