OM-IO-Link Master.044
01/21
IO Link Master - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All firmware and electronic files are provided by ifm.
To exchange an IO-Link device:
Requirements
> The new IO-Link device is in the default state, as on delivery (factory settings).
> The new IO-Link device supports the IO-Link standard 1.1 or higher.
1. Store the parameter set of the old IO-Link device
‣
Create the following parameter of the IO-Link port
Device validation and data storage = [Type compatible V1.1 device with Restore]
‣
Save the changes on the device.
> The IO-Link master saves the parameter values of the connected IO-Link device in the data memory.
2. Exchange IO-Link device
‣
Disconnect the old IO-Link device from the IO-Link master.
‣
Connect the new IO-Link device with the same IO-Link port of the NC-MP-4A4B-12DLA/AL1403.
> The IO-Link master transfers the parameter values from the data memory to the new IO-Link device.
> The new IO-Link device works with the restored parameter set.
11.3. Exchanging the IO-Link device