OM-IO-Link Master.022
01/21
IO Link Master - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All firmware and electronic files are provided by ifm.
With factory settings, the IO-Link master works in the DCP mode. In the DCP mode, the
configuration options are limited. For parameter setting with LR DEVICE, the IO-Link master and
the PC used for parameter setting must be configured for the same IP address range.
To access the NC-MP-4A4B-12DLA/AL1403 with LR DEVICE:
1. Preparations
‣
Install LR DEVICE on the PC (→ User documentation “LR DEVICE”)
‣
Establish Ethernet connection between PC and Port XF1 or XF2.
2. Start LR DEVICE and update the device library
‣
Start LR DEVICE.
‣
Update the device library.
> The device library contains the IO-Link device description file of the IO-Link master.
3. Look for IO-Link master
‣
Im LR DEVICE: Scan the network for devices.
> LR DEVICE searches the network for IO-Link masters and IO-Link devices.
> LR DEVICE shows IO-Link masters in the device tree.
4. Configure IP settings
‣
Click on (NC-MP-4A4B-12DLA/AL1403)
> LR DEVICE shows the DCP view of the IO-Link master.
‣
Adapt the IP settings of the IO-Link master.
‣
Save changed values on the device.
> LR DEVICE writes the changed values on the device.
> The IO-Link master can be configured.
9.1.2. First access with LR DEVICE to the IO-Link master