OM-IO-Link Master.026
01/21
IO Link Master - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All firmware and electronic files are provided by ifm.
To set the max. current intensity of the supply voltages US and UA of an IO-Link port:
‣
Select [Port x] menu (x = 1...8).
> The menu page shows the current settings.
‣
Set the following parameters as required:
9.1.8. IO-Link Ports: restrict current intensity
For the IO-Link ports X1...X4, the following features can be set:
• Max. current intensity of the supply voltage US
• Max. current intensity of the supply voltage UA
For the IO-Link ports X5...X8, the following features can be set:
• Max. current intensity of the supply voltage US
Name
Description
Possible values
[Current Limit Pin2 UA]*
Max. current intensity of the supply voltage UA on the port
(value in milliamps)
0
...
2000*
0 mA*
2000 mA
[Current Limit Pin1 + Pin4 US]
Max. current intensity of the supply voltage US on the port
(value in milliamps)
0
...
450*
...
2000
0 mA
450 mA
2000 mA
‣
Save changed values on the device.
* ... Factory setting