Error
Code
Message/Condition
Meaning/Correction
911
TCP port not available
Programming error. Contact Nordson technical support.
917
Checksum error
Noise in network. Check for loose connections or Ethernet cables routed
parallel to high voltage or VFDs.
918
Invalid frame error
Noise in network. Check for loose connections or Ethernet cables routed
parallel to high voltage or VFDs.
919
Invalid reply error
Noise in network. Check for loose connections or Ethernet cables routed
parallel to high voltage or VFDs.
920
Reply time-out
Noise in network. Check for loose connections or Ethernet cables routed
parallel to high voltage or VFDs.
921
Modbus exception
response
Programming error or remote hardware error. Check PLC functions.
925
Illegal Function exception
response
Programming error or remote hardware error. Check PLC functions.
926
Illegal Data Address
exception response
Programming error or remote hardware error. Check PLC functions.
927
Illegal Data Value
exception response
Programming error or remote hardware error. Check PLC functions.
928
Slave Device Failure
exception response
Programming error or remote hardware error. Check PLC functions.
−
Watchdog Fault (any
remote node controller
fault)
Control program in PLC is not running, or controller has no program installed.
NOTE:
This fault may be a normal response to removing electrical power from
the remote node.
Check the PLC mode selection switch. The switch should be in the run (up)
position.
Replace the PLC. The replacement must be pre-programmed or a program
must be downloaded and installed in the field.
Contact Nordson Industrial Coating Systems Customer Support for details.
−
Operation was successful Normal operation. No action required.
−
Illegal argument error
Programming error. Contact Nordson technical support.
−
Illegal state error
Programming error. Contact Nordson technical support.
−
Evaluation expired
Programming error. Contact Nordson technical support.
−
I/O error class
Programming error. Contact Nordson technical support.
Fieldbus protocol error
class
Programming error. Contact Nordson technical support.
Содержание Encore HD iControl 2
Страница 6: ...2022 Nordson Corporation 1609758 04 iv Table of Contents...
Страница 8: ...2022 Nordson Corporation 1609758 04 ii Change Record...
Страница 84: ...2022 Nordson Corporation 1609758 04 4 34 Troubleshooting...
Страница 102: ...2022 Nordson Corporation 1609758 04 6 12 Parts...
Страница 104: ...2022 Nordson Corporation 1609758 04 7 2 Drawings...
Страница 105: ......
Страница 106: ......
Страница 107: ......
Страница 108: ......
Страница 109: ......
Страница 110: ......
Страница 113: ......
Страница 114: ......