19
Installation and quick start commissioning guide - Commander ID300/302
5511 en - 2017.06 / a
CONNECTIONS
3.2 - Terminal block location
Power and control terminal blocks are all removable (relay, STO, control, AC power).
To avoid a fire hazard and maintain validity of the UL listing, adhere to the specified tightening
torques for the power and ground terminals.
•
Commander ID300/302 sizes 1 or 2
STO terminals
(1)
(1)
STO terminals are not enabled for
Commander ID300 drive (ID302 only)
(2)
If an ID-SIZEx-Brake contactor option is fitted,
refer to the specific terminal block location on next page
Relay terminals
Control terminals
Braking terminals
Ground terminals
AC power terminals
(2)
Small screwdriver
Maximum torque
setting: 0.5 N.m (0.37 Ib ft )
Torx 20 screwdriver
Maximum torque
setting: 2.5 N.m (1.84 Ib ft)
Philips screwdriver
Maximum torque
setting: 0.6 N.m (0.44 Ib ft)
EIA 485 serial comms
RJ45 connector
•
Commander ID300/302 size 3
Relay terminals
Control terminals
Braking terminals
Ground terminals
AC power terminals
(2)
Small screwdriver
Maximum torque
setting: 0.5 N.m (0.37 Ib ft )
RJ45 connector
EIA 485 serial comms
Module connector
Fieldbus or I/O module slot
Torx 20 screwdriver
Maximum torque
setting: 2.5 N.m (1.84 Ib ft)
Philips screwdriver
Maximum torque
setting: 0.6 N.m (0.44 Ib ft)
STO terminals
(1)
(1)
STO terminals are not enabled for
Commander ID300 drive (ID302 only)
(2)
If an ID-SIZEx-Brake contactor option is fitted,
refer to the specific terminal block location on
next page