20
Installation and quick start commissioning guide - Commander ID300/302
5511 en - 2017.06 / a
CONNECTIONS
•
Commander ID300/302 with ID-SIZEx-Brake Contactor option (drive size 1 or 2 shown)
STO terminals
(1)
(1)
STO terminals are not enabled for
Commander ID300 drive (ID302 only)
Relay terminals
Control terminals
Braking terminals
Ground terminals
AC power terminals
FFB brake terminals
Small screwdriver
Maximum torque
setting: 0.5 N.m (0.37 Ib ft )
Torx 20 screwdriver
Maximum torque
setting: 2.5 N.m (1.84 Ib ft)
Philips screwdriver
Maximum torque
setting: 0.6 N.m (0.44 Ib ft)
(Already connected at factory)
EIA 485 serial comms
RJ45 connector
3.3 -
Cable runs
CAUTION
•
The Commander ID300/302 is supplied with
IP55 protection. Only the use of IP55 or higher
cable glands, correctly installed, ensure that
this protection index is maintained. Optional kits
include all the cable glands needed for connection
of the standard product.
•
In order to preserve the motor’s original IP55
protection, it is essential to tighten the cable gland
seal correctly (so that it cannot be unscrewed by
hand)
•
Incorporate a bend where the cables enter the
cable glands so that water cannot penetrate the
terminal box.
Replace the plugs fitted on the holes which should be
used, with cable glands and their seals as specified in
the table below.
Source to
connect
Cable glands
Type
Dimensions
Mains supply input
Standard
or EMC
M25 or M20
Digital I/O
standard
or EMC
M16 or M20
Analog I/O
EMC
M16 or M20
Option cable gland kits are available to ease cable
connections.
NOTE
Keep the plug if the cable entry is not used.
3.4 - Cable sizes and fuses
• It is the responsibility of the user to
connect the Commander ID300/302 and fit
protective devices in accordance with the
le gislation and regulations in force in the country of
use. This is particularly important as regards the
size of the cables, the type and rating of fuses, the
earth or ground connection, powering down,
acknowledging trips, isolation and protection
against overcurrents.
• This table is given for information only, and must
under no circumstances be used in place of the
current standards.
The fuses types must be either IEC type gG or UL class
CC, J or T.
The circuit breakers must be UL listed class DIVQ/
DIVQ7.
Mains
supply
Max.
input
current
(A)
ID300
ref.
Fuse ratings Cable size
CEI
UL
mm
2
AWG
230V
1ph
4.5
12017
6
6
1
16
5.3
12024
6
6
8.1
12030
10
10
9.1
22035
16
15
1.5
12
12
22052
16
15
2.5
10
14.3
22057
20
20
2.5
/ 4
10