8
Installation and quick start commissioning guide - Commander ID300/302
5511 en - 2017.06 / a
GENERAL INFORMATION
1.3 -
Environmental characteristics
Characteristics
Level
Environmental protection
rating
IP55
Operating ambient air
temperature
• -16°C (3.2°F) to 40°C (104°F)
• Up to 50°C (122°F) with derating (current derating of 1% per additional Celsius
degree from 40°C). For more information, please contact Leroy-Somer.
Storage and transport
temperature
• Storage time is 2 years at temperature between -15°C (5°F) and 55°C (131°F). As
drive low voltage capacitors cannot be reformed due to their location, it is therefore
recommended that drives are powered up for a minimum of 1 hour after every 2
years of storage. This process allows the drive to be stored for a further 2 years.
• Motor greasing: After a maximum of 3 year storage, replace the bearings (bearings
which cannot be re-greased)
• Brake motor: every 6 months period of storage, disconnect the brake power supply
unit (++,- or +,- terminal block from ID-SIZEx-Brake Contactor option) and check the
winding insulation resistance (phase/earth resistance higher than 10 MΩ). Drain any
condensation water.
• As a general rule, machines must be stored in a horizontal position, in a dry
location protected from harsh weather conditions, free from vibration, dust and
corrosive gases. At relative humidity levels above 90%, the motor insulation can
drop very quickly and become virtually non-existent at around 100%. The state of
the anti-rust protection on unpainted motor parts should be monitored. During
storage the motor drain plugs must be removed to allow condensation water to
escape. For long storage periods, place the machine in a sealed package (for
example heat-shrunk plastic) containing sachets of desiccant.
• If the storage location is subject to vibration, try to reduce the effect of this vibration
by placing the machine on a damping support (rubber plate or similar).
Turn the rotor a fraction of a turn once a fortnight to prevent the bearing rings from
becoming marked.
Relative Humidity
5 to 90% (non-condensing).
Altitude
• < 1,000 m (3,300 ft) without derating.
• 1,000 m to 3,000 m (3,300 ft to 9,900 ft) above sea level: de-rate the maximum
output current from the specified figure by 1% per 100 m (330 ft) above 1,000 m
(3,300 ft).
For example at 3,000 m (9,900 ft), the output current of the drive would have to be
de-rated by 20 %.
For more information, please contact Leroy-Somer.
Pollution
Dry, non-conductive pollution only (pollution degree 2 according to IEC 60664-1).
Vibration
Meets the requirements of EN 61800-5-1, Table 27 and EN 50178 test 9.4.3.2
RoHS Directive immunity Meets EU Directive 2011/65/EU
EMC
• Conforms to C3 level of EN 61800-3 + A1 (2012) for Commander ID300
• Conforms to C3 level of EN 61800-3 + A1 (2012) and EN 61326-3-1
+ EN 61000-6-7 for Commander ID302
UL standards
Conforms to UL 61800-5-1_1 (except for associations with brake motors). The file
number is E211799.