Installation and quick start commissioning guide - Commander ID300/302

5511 en - 2017.06 / a

 

SAFETY AND OPERATING INSTRUCTIONS FOR VARIABLE SPEED DRIVES

(In accordance with the low voltage directive 2014/35/EU)

Throughout the manual, this symbol warns 

of  consequences  which  may  arise  from 

inappropriate use of the 

Commander  ID300/302  (motor  or  drive),  since 

electrical  risks  may  lead  to  material  or  physical 

damage as well as constituting a fire hazard.

1 - General

Depending on their degree of protection, the 

Commander ID300/302 may contain unprotected live 

parts, which may be moving or rotating, as well as hot 

surfa ces, during operation.

Unjustified  removal  of  protection  devices,  incorrect 

use, faulty installation or inappropriate operation could 

re present a serious risk to personnel and equipment.

For further information, consult the manual.

All work relating to transportation, installation, 

commissioning and maintenance must be performed 

by  experienced,  qualified  personnel  (see  IEC  364, 

CENELEC HD 384 or DIN VDE 0100, as well as 

national  specifications  for  installation  and  accident 

prevention).

In these basic safety instructions, qualified personnel 

means persons competent to install, mount, 

commission and operate the product and possessing 

the relevant qualifications.

2 - Use

Commander ID300/302 motors and drives are 

components designed for integration in installations or 

electrical machines.

When integrated in a machine, commissioning must 

not take place until it has been verified that the machine 

conforms with directive 2006/42/EC (Machinery 

Directive). It is also necessary to comply with standard 

EN 60204, which stipulates in particular that electrical 

actuators (which include Commander ID300/302) 

cannot be considered as circuit-breaking devices and 

certainly not as isolating switches.

Commissioning can take place only if the requirements 

of the Electromagnetic Compatibility Directive (EMC 

2014/30/EC) are met.

The Commander ID300/302 meet the requirements of 

the Low Voltage Directive 2014/35/EU. The harmonized 

standards of the DIN VDE 0160 series in connection 

with standard VDE 0660, part 500 and EN 60146/VDE 

0558 are also applicable.

The technical characteristics and instructions 

concerning the connection conditions specified on the 

nameplate and in the documentation provided must be 

observed without fail.

3 - Transportation, storage

All instructions concerning transportation, storage and 

correct handling must be observed.

The  climatic  conditions  specified  in  the  technical 

ma nual must be observed.

4 - Installation

The installation and cooling of equipment must comply 

with the specifications in the manual supplied with the 

product.

Commander ID300/302 must be protected against 

any excessive stress. In particular, there must be no 

da mage to parts and/or modification of the clearance 

between components during transportation and 

handling. Avoid touching the electronic components 

and contact parts.

The Commander ID300/302 contain parts which are 

sensitive to electrostatic stresses and may be easily 

da maged if handled incorrectly. Electrical components 

must not be exposed to mechanical damage or 

destruction (risks to health!).

5 - Electrical connection

When work is performed on Commander ID300/302 

which are powered up, the national accident prevention 

regulations must be respected.

The electrical installation must comply with the relevant 

specifications  (for  example  conductor  cross-sections, 

protection via fused circuit-breaker, connection of 

protective conductor). More detailed information is 

given in the manual.

Instructions for an installation which meets the 

requirements for electromagnetic compatibility, 

such  as  screening,  earthing,  presence  of  filters 

and correct insertion of cables and conductors, 

are given in the documentation supplied with the 

Commander ID300/302. These instructions must be 

followed in all cases, even if the Commander ID300/302 

carries the CE mark.

Adherence to the limits given in the EMC legislation is 

the responsibility of the manufacturer of the installation 

or the machine.

6 - Operation

Installations incorporating Commander ID300/302 

must be fitted with additional protection and monitoring 

devi ces as laid down in the current relevant safety 

regulations, such as the law on technical equipment, 

accident  prevention  regulations,  etc.  Modifications  to 

the Commander ID300/302 using control software are 

permitted.

Active parts of the device and the live power 

connections must not be touched immediately after 

the Commander ID300/302 is powered down, as the 

capacitors may still be charged. In view of this, the 

warnings  fixed  to  the  variable  speed  drives  must  be 

observed.

During operation, all doors and protective covers must 

be kept closed.

7 - Servicing and maintenance

Refer to the manufacturer’s documentation.

This manual is to be given to the end user.

Содержание LEROY-SOMER Commander ID30 Series

Страница 1: ...Commander ID300 302 Installation and quick start commissioning guide Integrated drive for IMfinity motors with or w o brake Reference 5511 en 2017 06 a...

Страница 2: ...the motor or the machine are not mechanically designed to withstand such speeds the user may be exposed to serious danger resulting from their mechanical deterioration Before programming a high speed...

Страница 3: ...erved without fail 3 Transportation storage All instructions concerning transportation storage and correct handling must be observed The climatic conditions specified in the technical ma nual must be...

Страница 4: ...Coupling 17 2 6 Brake motor option specificities 17 3 CONNECTIONS 18 3 1 Terminal block access 18 3 2 Terminal block location 19 3 3 Cable runs 20 3 4 Cable sizes and fuses 20 3 5 Power connections 2...

Страница 5: ...allowing easy commissioning for users who are already familiar With the benefit of Leroy Somer expertise in motor and drive solution the Commander ID300 302 integrates a high performance motor contro...

Страница 6: ...rque N m Coil current mA Motor 3 Three phase A C motor LSES Series 112 Frame size MU Housing designation and manufacturer index T Impregnation index N 123456 Motor serial number A Month of production...

Страница 7: ...es 4 models External EMC filter available soon Cable entry side flanges 2 models Brake Control option Optional Keypads To be mounted by the user Other options are factory fitted Size 3 Optional Brakin...

Страница 8: ...insulation can drop very quickly and become virtually non existent at around 100 The state of the anti rust protection on unpainted motor parts should be monitored During storage the motor drain plug...

Страница 9: ...ion 1 4 2 Efficiency IES2 level according to EN 61800 9 2 Overload 150 of the full rated output current for 60 seconds or 180 for 3 seconds 10 times per hour Mains supply voltage and frequency 200 V d...

Страница 10: ...ity Motor Voltage Max input current Size Ref Output Current 4 poles IE2 4 poles IE3 2 poles IE3 Output power V A A kW Hp 400V 3 ph 3 4 1 14021 2 1 LSES 80LG LSES 80LG LSES 80L 0 75 1 0 3 5 14025 2 5 L...

Страница 11: ...d drive The motor and drive leakage current values are as follows With size 1 or 2 drive 2 1 mA AC at 230 V 50 Hz corner delta earth to ground 1 5 mA AC at 230 V 50 Hz line to neutral supply star poin...

Страница 12: ...s some special measures may be required to prevent malfunction or damage Surges may be caused by lightning or severe power faults in association with grounding arrangements which permit high transient...

Страница 13: ...nected to drive control terminal 1 to 3 3 LED connected to drive control terminal 5 See above for LED functionalities ID LED FLANGE 3 LED connected to drive control terminal 5 See above for LED functi...

Страница 14: ...tor commands Parameter settings Mounting arrangement replaces standard terminal cover new drive dimensions H 24 5 mm This option has to be mounted by the user Please refer to the relevant mounting doc...

Страница 15: ...mply with the applicable legislation and regulations and codes of practice in the country in which the equipment is used The drive contains capacitors that remain charged to a potentially lethal volta...

Страница 16: ...0 9 LSES 132 M MU 200 180 150 14 2 3 Assembly The motor with integrated Commander ID300 302 drive is fitted to the machine like a standard motor with flange or foot mounting The motor ventilation cool...

Страница 17: ...d to the length of the key Machining of visible parts protruding from the key CONFORMING MOUNTINGS NON CONFORMING MOUNTING Non machined open keyway Coupling not adapted to the length of the key Part t...

Страница 18: ...to the AC supply by a plug and socket The AC supply terminals of the drive are connected to the internal capacitors through recti fier diodes which are not intended to give safety isolation If the plu...

Страница 19: ...ound terminals AC power terminals 2 Small screwdriver Maximum torque setting 0 5 N m 0 37 Ib ft Torx 20 screwdriver Maximum torque setting 2 5 N m 1 84 Ib ft Philips screwdriver Maximum torque setting...

Страница 20: ...glands so that water cannot penetrate the terminal box Replace the plugs fitted on the holes which should be used with cable glands and their seals as specified in the table below Source to connect C...

Страница 21: ...circuit capable of delivering not more than 5000 rms symmetrical Amperes 480V or 230V maximum when protected by fuses as specified above 3 5 Power connections It is compulsory to connect the motor to...

Страница 22: ...a personal computer an additional isolating barrier must be included in order to maintain the SELV classification If any of the digital inputs including the drive enable or STO inputs are connected in...

Страница 23: ...tons ID RUN POT LED FLANGE option DI3 and DI4 are already connected If the user wants to disable Run reverse function Pr 00 028 should be set to 0 NOTE The Commander ID300 302 is delivered with the st...

Страница 24: ...50 A Resolution 11 bits Sample rate 4 ms Load impedance 165 k Operating as digital input Impedance 6 8 k Input threshold 10 V 0 8 V IEC 61131 2 Type 1 Operating as voltage output Full scale voltage ra...

Страница 25: ...motor with a very high level of integrity It is suitable for incorporation into a safety system for a machine The safety function is active when either one or both STO inputs are in the logic low sta...

Страница 26: ...en designed to connect the drive to IT equipment such as laptop computers and is available from the supplier of the drive part number 4500 0096 The isolated serial communications lead has reinforced i...

Страница 27: ...The green LED must be permanent supply OK Close the Enable terminal 8 or the STO terminals 31 34 CAUTION In the case the red LED is active permanent or flashing the drive is in a trip or alarm state T...

Страница 28: ...utton Green 7 Status LED ID SIZEx Keypad 1 only 1 ID SIZEx Keypad can be either ID SIZE1 Keypad or ID SIZE3 Keypad 4 2 2 How to read or edit parameters By default only the first 10 parameters of Menu...

Страница 29: ...he drive is not enabled i e drive is in Inhibit state 2 Select Reset 50 Hz Defs in Pr 00 000 3 Press the red reset button of the keypad NOTE Motor parameters Pr 00 006 to Pr 00 009 are factory set The...

Страница 30: ...30 Pr 10 031 and Pr 10 061 should be set correctly otherwise premature Brake R Too Hot trips may be seen Pr Braking Resistors ID SIZE1 DBR200 ID SIZE3 DBR400 10 030 0 1 0 2 10 031 600 600 10 061 200 1...

Страница 31: ...2 021 Deceleration Rate 10 0 s 100 Hz 00 005 11 034 Drive Configuration STANDARD AV AI AV with brake 3PS 1Ana brake 3PS 1Ana Nobrake 8 Presets Keypad Keypad Ref Electronic Pot Torque Control Pid Contr...

Страница 32: ...Stop Mode Coast Ramp Ramp dc I dc I Timed dc I Disable Ramp 00 032 05 013 Dynamic V to F Select 0 or 1 1 00 033 06 009 Catch A Spinning Motor Disable Enable Fwd Only Rev Only Disable 00 034 01 010 Bi...

Страница 33: ...Enable Disable Relay Digital IO User Disable Common parameters 00 056 10 020 Trip 0 0 to 255 00 057 10 021 Trip 1 0 to 255 00 058 10 022 Trip 2 0 to 255 00 059 11 047 Onboard User Program OUP Enable S...

Страница 34: ...the trips and their explanations please refer to the user and technical guide ref 5512 www commanderID300 info If the drive trips on a fault or is in alarm state a keypad option or Connect tool softw...

Страница 35: ...nation parameter This trip indicates that destination output parameters of two or more logic functions Menus 7 and 8 within the drive are writing to the same parameter External Trip External trip is i...

Страница 36: ...In any mode an alarm is an indication given from the flashing red LED of the flange option or on the keypad display by alternating the alarm string with the drive status string display If an action is...

Страница 37: ...with on line monitoring of program variables with user defined watch windows and help for on line change of program in line with current PLC practices To get the file of the Machine Control Studio sof...

Страница 38: ...er possible causes incorrect settings drive malfunction refer to the Commander ID300 302 user and technical guide ref 5512 Motor heats abnormally faulty ventilation check the environment clean the fan...

Страница 39: ...ducing dust and particles under the seals CAUTION Do not dismantle the Commander ID300 302 while it is still under guarantee as this would then immediately become null and void Certain components whic...

Страница 40: ...Moteurs Leroy Somer Headquarter Boulevard Marcellin Leroy CS 10015 16915 ANGOUL ME Cedex 9 Limited company with capital of 65 800 512 RCS Angoul me 338 567 258 www leroy somer com...

Отзывы: