11
Installation and quick start commissioning guide - Commander ID300/302
5511 en - 2017.06 / a
GENERAL INFORMATION
Commander ID300/302
with non IE or IE3 motors and brake
Supply
Commander
ID300/302 drive
LS or IMfinity
®
Motor
Voltage
Max
input
current
Size
Ref.
Output
Current
Brake
type
4 poles - NIE
4 poles - IE3
Output
power
(V)
(A)
(A)
kW
Hp
400V
3 ph
1.6
1
14012
1.2
FFB1
LS 71M
(1)
-
0.25 0.33
2.2
14015
1.5
FFB1
LS 71M
(1)
-
0.37
0.5
2.9
14018
1.8
FFB1
LS 71L
(1)
-
0.55 0.75
3.4
14021
2.1
FFB1
LS 80L
(1)
LSES 80LG
(1)
0.75
1.0
3.5
14025
2.5
FFB1
LS 80L
(1)
LSES 80LG
(1)
0.9
1.25
3.5
14030
3.0
FFB2
LS 90SL
(1)
LSES 90SL
(1)
1.1
1.5
3.9
14033
3.3
FFB2
LS 90L
(1)
LSES 90LU
(1)
1.5
2.0
7
2
24042
4.2
FFB2
LS 90L
(1)
LSES 100L
(1)
1.8
2.4
7.5
24050
5.0
FFB2
LS 100L
(1)
LSES 100LR
(1)
2.2
3.0
8
24070
7.0
FFB3
LS 100L
(1)
LSES 100LG
(1)
3.0
4.0
9.5
24085
8.5
FFB3
LS 112MG
(1)
LSES 112MU
(1)
4.0
5.0
13
3
34119
11.9
FFB3
LS 132S
(1)
-
5.5
7.5
FFB4
-
LSES 132SM
(1)
5.5
7.5
16
34155
15.5
FFB4
LS 132M
(1)
LSES 132MU
(1)
7.5
10.0
: Standard motor and drive associations
(1)
For these drive and motor associations, a drive fan is fitted as standard. If it is a gear-motor, the fan is only fitted
on size 3 drive (5.5 to 7.5 kW).
1.5 - Earth leakage current
1.5.1 - Ground leakage of the motor and drive
The motor and drive leakage current values are as
follows:
With size 1 or 2 drive:
• 2.1 mA* AC at 230 V 50 Hz (corner delta earth to
ground)
• 1.5 mA* AC at 230 V 50 Hz (line to neutral supply, star
point ground)
• 37.5 mA* AC at 525 V 50 Hz (corner delta earth to
ground)
• 12.6 mA* AC at 525 V 50 Hz (line to neutral supply,
star point ground)
With size 3 drive:
• 2.6 mA* AC at 230 V 50 Hz (corner delta earth to
ground)
• 1.5 mA* AC at 230 V 50 Hz (line to neutral supply, star
point ground)
• 14.7 mA* AC at 525 V 50 Hz (corner delta earth to
ground)
• 7.8 mA* at 525 V 50 Hz (line to neutral supply, star
point ground)
*Proportional to the supply voltage and frequency.
•
When the leakage current is high
(> 3.5 mA), a permanent fixed ground
connection must be provided or other
suitable measures taken to prevent a safety hazard
occurring if the connection is lost. For more details,
please refer to section 3.5.
•
The Commander ID300/302 integrates an internal
EMC filter, but there is no possibility to disconnect
it. If the ground leakage current is unacceptable for
the user, please contact Leroy-Somer.
1.5.2 - Use of earth leakage detector (RDC)
A type B RCD , able to detect AC and pulsating DC fault
currents, can be used with the Commander ID300/302.
If an external EMC filter is used, a delay of at least
50 ms is recommended to avoid spurious tripping. The
leakage current is likely to exceed the trip level if all of
the phases are not energized simultaneously.