15
Installation and quick start commissioning guide - Commander ID300/302
5511 en - 2017.06 / a
MECHANICAL INSTALLATION
Type
Option
Name
Details
I/O expansion
ID-SIZE1-I/O
• For size 1 and 2 drives, use ID-SIZE1-I/O
Increases the I/O capability
Mounting arrangement: replaces standard terminal
cover (new drive dimensions: H + 41.5 mm). This option
has to be mounted by the user. Please refer to the
relevant mounting documentation. A fieldbus option
cannot be fitted at the same time.
SI-I/O module
• For size 3 drive: fieldbus module.
Increases the I/O capability
Mounting arrangement: This option has to be fitted to
the option slot and connected by the user. Please refer
to the relevant mounting documentation. A fieldbus
option cannot be fitted at the same time.
Brake
control
ID-SIZE1-
Brake
Contactor
ID-SIZE3-
Brake
Contactor
• For size 1 and 2 drives, use ID-SIZE1-Brake
Contactor
• For size 3 drive, use ID-SIZE3-Brake Contactor
Mounting arrangements: factory-fitted inside the drive
Allows the drive to easily control a motor with FFB
brake by using a dedicated drive preset configuration
(“AV with brake” or “3PS/1Ana brake”). For connection
details, see section 3.5.
External
EMC filter
ID-SIZE1-EMC
filter LV-LL or
HV-LL
ID-SIZE3-EMC
Filter HV-LL
Allows the drive to conform to C1 level according to
EN61800-3 + A1 (2012) (available soon)
2 - MECHANICAL INSTALLATION
•
The mechanical and electrical installation
instructions must be adhered to. Any
questions or doubt should be referred to
the supplier of the equipment. It is the
responsibility of the owner or user to ensure that
the installation of the Commander ID300/302 and
any external option unit, and the way in which they
are operated and maintained, comply with the
applicable legislation and regulations and codes of
practice in the country in which the equipment is
used.
•
The drive contains capacitors that remain
charged to a potentially lethal voltage after the AC
supply has been disconnected. If the drive has
been energized, the AC supply must be isolated
at least 10 minutes before work may continue.
Normally, the capacitors are discharged by an
internal resistor. Under certain, unusual fault
conditions, it is possible that the capacitors may
fail to discharge, or be prevented from being
discharged by a voltage applied to the output
terminals. If the drive has failed in a manner that
causes the keypad display (if present) to go blank
immediately, it is possible the capacitors will not be
discharged. In this case, consult Leroy-Somer or
an authorized distributor.
•
The Commander ID300/302 and its options must
be installed by professional assemblers who are
fami liar with the requirements for safety and EMC.
The assembler is responsible for ensuring that
the end product or system complies with all the
relevant laws in the country where it is to be used.
•
When the cover is open, the
Commander ID300/302 degree of protection
is IP10. Any work should only be carried out
by experienced, qualified personnel. The
Commander ID300/302 must not be opened whilst
energized.
•
Holes are provided at the lowest points of the
enclosure, depending on the operating position,
to drain off any moisture that may have been
accumulated inside during cooling of the machine.
In conditions which encourage the formation of
condensation, it is advisable to leave the drain
holes permanently open.
2.1 - Checks on receipt
Before installing the Commander ID300/302, check
that:
- The motor and drive have not been damaged during
transport,
- The information on the nameplates is compatible with
the power supply.
For nameplate details, please refer to section 1.2.