Technical specifications
IP 21
Class 3
Boiler class according to EN 303-5
942 mm (increases 24 – 39 mm)
Height without base
1100 mm
Required ceiling height
526 mm
Width
800 mm
Depth
220 kg
Weight
60 litres
Volume total
230 V NAC 50 Hz
Supply voltage
10 A
Fuse
1100 W
Base power requirement
11 W
Current consumption control unit
IP 21
Enclosure class
0.25MPa (2.5 bar)
Max permitted pressure in the boiler
0.25MPa (2.5 bar)
Cut-off pressure in the boiler
20 kW
Max available output pellet operation
6 -20 kW
Output range pellet operation
18.7kW
Nominal heating output pellet mode
4.15kg/timme
Combustion period pellet mode at Q
N
60 litres
Hearth, volume
13 litres
Ash box, volume
60 litres
Water volume
22 litres
Capacity for charging chamber (grille installed)
15 -25 Pa
Draught requirement
150 mm
Flue diameter
130 °C
Exhaust temp. at nominal & minimal heating output
Qn 0.01375kg/sek.
Exhaust mass flow at nominal heating output
Qm 0.01027kg/sek.
Exhaust mass flow at minimum heating output
250Pa (2.5 mbar)
Resistance water side at 20 K
880Pa (8.8 mbar)
Resistance water side at 10 K
85 °C
Max work temp.
50 - 80 °C
Setting range, temp. control
60 °C
Minimum temp. return line
300 l, 469 x 553 mm (Part no. 634533)
Pellet store capacity and opening dimension.
500 litres 469 x 1000 mm (Part no. 634532)
Pellet store capacity and opening dimension.
Wood pellets
Fuel type
6 - 10 mm
Size
<10%
Moisture
PELLUX 100
66
For the Installer
Technical specifications
Содержание PELLUX 100
Страница 1: ...INSTALLATION AND MAINTENANCE INSTRUCTIONS MOS GB 1411 1 PELLUX 100 331139 PELLUX 100 APH...
Страница 2: ......
Страница 63: ...Burner 61 PELLUX 100 For the Installer Electrical circuit diagram...
Страница 74: ...PELLUX 100 72...
Страница 75: ......