Burner settings
Description
Function
Activate continuous fuel feed
here, regardless of other set-
tings.
Feed fuel
Gives permission to the con-
trol computer to start the
burner.
Burner on
Determines what type of fuel
is used.
Fuel type
Service settings burner
Description
Function
Minimum amount of air when
controlling when the burner
runs at 30 % output or in
power 1.
Air volume min.
Maximum amount of air dur-
ing control when the burner
runs at 100 % output or in
power 2.
Air volume max.
Maximum time for fuel feed
during control when the
burner runs at 100 % output
or in power 2, every 20
seconds.
Feed max.
Burner minimum output dur-
ing control or in power 1.
Output min. (FL2)
Burner maximum output dur-
ing control or in power 2.
Output max. (FL2)
Burner working method dur-
ing controlled output (Fuzzy
Logic 2) or step controlled in
± 2 °C.
Modulation type
The light level in the burner
where the control computer
detects a flame.
Photocell stepval.
Test run the ignition function.
Firing up test*
Test run feeding fuel to the
burner.
Burner feed test*
Test run the pellet screw from
the pellet hopper to the burn-
er.
Test pellet screw*
Test run the burner fan.
Test fan*
Test run what weight of fuel
is supplied from the pellet
hopper during continuous
operation for 1 hour.
Test fuel mass
Calorific value of burnt fuel
(kWh/kg).
Fuel calorific value
The lambda sensor determines
if the control computer must
change any control values in
relation to the amount of
oxygen in the flue gas.
Lambda control
Description
Function
Set value for oxygen content
of the smoke gas minimum
30 % burner output.
Oxygen level min.
Set value for oxygen content
of the smoke gas minimum
100 % burner output.
Oxygen level max.
Time span for fuel feed during
the firing up sequence.
Start dose
Time interval between burner
cleaning.
Sweeping period
Number of times that grid
cleaning is to be carried out.
Sweeping cycles
Setting burner output.
Exhaust fan power
Test operation of grid clean-
ing.
Grid cleaning test
Grid cleaning only occurs in
conjunction with cleaning the
heat exchanger. (Boiler/Ser-
vice).
Grid silent cleaner
* Units in the burner menu can only be test run when the
control computer is in OFF mode.
** Exhaust fan must be connected to an additional module
(module 7).
For setting schedule see page 43.
PELLUX 100
40
For the Installer
Service