Accessories
Connecting modules
All connected accessories must go via an extra module. To
connect all accessories available for Pellux 100, seven extra
modules are required.
Modules 0 - 4 are used for different heating coils.
Different accessories are connected to module 5, e.g. solar
heating, accumulator, return water temp. and external
hot water pump.
Module 6 is a standard module that is always installed in
the boiler to manage direct connection of different func-
tions for example, CAN-bus, hot water etc.
The Lambda module is preconfigured and only for Lambda
control.
The different accessories are connected to respective
module and then connected to a CAN-bus, which is con-
nected to the control computer via module 6.
Modules 0 - 5 are in an external cabinet close to Pellux100.
The Lambda module is in the boiler level with module 6.
NOTE
Only the Lambda module may be placed in the boiler,
all other modules must be placed in a separate cab-
inet.
When a module for an accessory is connected, the
dipswitch must be set (not applicable to the Lambda
module) so that the control computer can control the new
accessory or use its information to control another part of
the boiler.
The dipswitch setting gives the module a unique address.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
27 28 29 30 31 32 3334 35 36 37 38 39 40 41 4243 44 45 46 4748 49 50 51 52
Dipswitch
The switches are numbered 1 to 4. Switches 1, 2 and 3 are
used to give the module a unique number. Switch 4 is for
termination.
Switch 1 has a value of 1, switch 2 has a value of 2 and
switch 3 has a value of 4, which means, to give a module
an address corresponding to module 5, set switches 1 and
3 to on and switch 2 to off. See table below.
1 2 3 4
ON
1 2 4 T
Module num-
ber
Dipswitch number (
value
)
3 (
4
)
2 (
2
)
1 (
1
)
Module 0
OFF
OFF
OFF
Module 1
OFF
OFF
ON
Module 2
OFF
ON
OFF
Module 3
OFF
ON
ON
Module 4
ON
OFF
OFF
Module 5
ON
OFF
ON
Module 6
(standard
module)
ON
ON
OFF
Lambda mod-
ule
ON
ON
ON
NOTE
It is important to set the last module as a termination
module otherwise there is a risk of echoes in the CAN
bus, which can mean incorrect control of the boiler.
Switch number 4 is used to set the termination.
The system must have a termination at each end, one on
the standard module (module 6) and one on the module
positioned furthest away from module 6. Switch 4 must
only be in the On position on module 6 and on the module
that is connected furthest away from module 6. The
Lambda module has a termination jumper and does not
have a switch.
Master
I/O
I/O
I/O
I/O
1
T=OFF
0
T=OFF
2
T=OFF
6
T=ON
T=ON
Module 6
Lambda
2
1
0
T=On
T=Off
T=Off
T=Off
T=On
PELLUX 100
44
For the Installer
Service