![NANOTEC ELECTRONIC N5 Скачать руководство пользователя страница 138](http://html.mh-extra.com/html/nanotec-electronic/n5/n5_technical-manual_705153138.webp)
Technical Manual N5 (CANopen)
10 Description of the object dictionary
Note
If the CAN-ID is not to correspond to the default value of 80
h
, it must be ensured that only not-yet
unassigned or reserved CAN-IDs are used.
Object description
Index
1005
h
Object name
COB-ID Sync
Object Code
VARIABLE
Data type
UNSIGNED32
Savable
yes, category: communication
Access
read / write
PDO mapping
no
Allowed values
Preset value
00000080
h
Firmware version
FIR-v1426
Change history
1007h Synchronous Window Length
Function
This object contains the length of the time window in microseconds for synchronous PDOs. If the
synchronous time window has elapsed, all synchronous TxPDOs are rejected and an EMCY message
sent. The RxPDOs are also rejected up to the next SYNC message.
The value "0" switches off the time window, thereby allowing the PDOs to be sent at any time.
This object is only available in device variants with CANopen connection.
Object description
Index
1007
h
Object name
Synchronous Window Length
Object Code
VARIABLE
Data type
UNSIGNED32
Savable
yes, category: communication
Access
read / write
PDO mapping
no
Allowed values
Preset value
00000000
h
Firmware version
FIR-v1426
Change history
1008h Manufacturer Device Name
Function
Contains the device name as character string.
Version: 2.0.1 / FIR-v1650