Emergency stop sequence
If an emergency stop command is activated, the following steps are carried out automatically:
1. Closing gas supply solenoid valves
2. Closing mixture throttles
3. Engine running down to standstill
4. Deactivating ignition
5. Requesting external ventilation by contact
Restarting after emergency stop
A scavenging phase and a request for external ventilation by contact ensue following a start request
after emergency shutdown.
1. Requesting external ventilation by contact
2. Activating starter
3. Waiting for starting speed
4. Flushing the engine
5. Disengaging starter
6. Engine running down to standstill
7. Resetting start counter
8. Awaiting start request
Oil refill sequence
1. Waiting for engine running
2. Engine running for a minimum (programmed) time period
3. Oil refilling enabled
4. When oil refill request is received
5. Refilling oil (automatically)
6. When oil refill request is canceled
7. Stopping oil refilling (automatically)
MS15027/00E 2013-10
| Operation | 39