932 – AL MIC5 Yellow
Yellow alarm.
Associated parameter 1.4520.933
Cause
Corrective action
An internal combined alarm in
the ignition system was
detected.
u
Precise error name is sent to the genset control via CAN bus.
933 – AL MIC5 Red
Red alarm.
Associated parameter 1.4520.936
Cause
Corrective action
An internal combined alarm in
the ignition system was
detected.
u
Precise error name is sent to the genset control via CAN bus.
934 – AL MIC5 Comm Lost
Red alarm.
Associated parameter 1.4520.939
Cause
Corrective action
CAN bus communication to
ignition system faulty.
1. Check cabling.
2. Check power supply.
3. Restart ECU, EMU & knock control.
4. Check settings using device-specific dialog software (in device).
948 – AL ESI activated
Red alarm.
Associated parameter 2.8006.044
Cause
Corrective action
Emergency stop input is
activated.
1. Rectify the fault causing the alarm.
2. Check cabling.
972 – AL MIC5 Signature difference
Red alarm.
Associated parameter 1.450.969
Cause
Corrective action
The ignition system has not
taken on the configuration from
the engine governor.
1. ECU restart
2. Check configuration in the ECU
144 | Troubleshooting | MS15027/00E 2013-10
TIM-ID: 0000044567 - 001