972 – AL MIC5 Signature difference
Red alarm.
Associated parameter 1.450.969
Cause
Corrective action
The ignition system has not
taken on the configuration from
the engine governor.
1. ECU restart
2. Check configuration in the ECU
972 – AL MIC5 Signature difference
Red alarm.
Associated parameter 1.450.969
Cause
Corrective action
The ignition system has not
taken on the configuration from
the engine governor.
1. ECU restart
2. Check configuration in the ECU
974 – AL CAN3 Bus Off
Yellow alarm.
Associated parameter 2.0500.692
Cause
Corrective action
CAN controller 3 is in "Bus-Off"
status. Bus nodes (ignition,
knock module, throttles or gas
mixer) have faults.
u
Check operation of nodes and cabling.
975 – AL CAN3 Error Passive
Yellow alarm.
Associated parameter 2.0500.693
Cause
Corrective action
CAN controller 3 has indicated a
warning. Bus nodes (ignition,
knock module, throttles or gas
mixer) have faults.
u
Check operation of nodes and cabling.
976 – AL CAN4 Bus Off
Yellow alarm.
Associated parameter 2.0500.694
Cause
Corrective action
CAN controller 4 is in "Bus-Off"
status. Bus nodes (ignition,
knock module, throttles or gas
mixer) have faults.
u
Check operation of nodes and cabling.