694 – SD T-Gas
Yellow alarm.
Associated parameter 1.8004.123
Cause
Corrective action
Gas temperature sensor
defective, short circuit or wire
break.
1. Not available in all engine versions (optional).
2. Check sensor and cabling (B38), replace as necessary.
719 – AL T-Gas L1
Yellow alarm.
Associated parameter 2.8006.034
Cause
Corrective action
Limit value 1 exceeded.
u
Check gas supply.
720 – AL T-Gas L2
Yellow alarm.
Associated parameter 2.8006.035
Cause
Corrective action
Limit value 2 exceeded.
u
Check gas supply.
842 – AL FuelThrottlePosition L1
Yellow alarm.
Associated parameter 2.8006.038
Cause
Corrective action
Tecjet throttle position has
exceeded limit value 1.
u
Check gas supply.
848 – AL Rel. air humidity L1
Yellow alarm.
Associated parameter 2.8006.039
Cause
Corrective action
Calculated air humidity has
exceeded limit value 1.
u
Check air humidity.
891 – AL Purging active
Yellow alarm.
Associated parameter 2.1090.048
Cause
Corrective action
Engine was stopped with
emergency stop or did not finish
starting successfully on several
occasions.
u
None
MS15027/00E 2013-10
| Troubleshooting | 143