![MSA Senscient ELDS 1000 series Скачать руководство пользователя страница 43](http://html.mh-extra.com/html/msa/senscient-elds-1000-series/senscient-elds-1000-series_operating-manual_1846249043.webp)
Installation Design & Engineering
Senscient ELDS™
Rev 15
43
GB
Arrangement for Multiple Cross-Duct ELDS™ Systems
For applications where three (3) or more Cross-Duct units are required it is necessary to ensure
that the maximum possible separation occurs between Rx units. The recommended arrangement
for 3 systems in a duct is illustrated below.
Here 3 ELDS™ cross-duct systems are mounted at a common location in a duct of width w. The
‘middle’ system is mounted with the beam in the opposite direction to the top and bottom systems
so it cannot interfere with either of the other two units and they cannot interfere with it. There is a
possibility of interference between the two units that are mounted in the common direction
however. The angular separation between these two units (top and bottom) is approximately given
by the following relation:
Π
×
=
w
d
180
θ
where is the angle (in degrees) between the two transmitters pointing in the same direction and
(Pi) is 3.142.
Senscient recommends that the value of be at least 10 degrees.
As an example, for a duct of width (w) of 2.5 metre the angular recommendation above would
require that the separation of the top and bottom Rx units be at least 0.44m.
In another example, for a duct width of 5m the angular recommendation would require a value of d
of at least 0.87m.
Tx
Rx
Tx
Tx
Rx
Rx
d
w
Содержание Senscient ELDS 1000 series
Страница 1: ...Operating Manual Senscient ELDS 1000 2000 Series Open Path Cross Duct Gas Detectors A 5170 0 Rev 15 ...
Страница 58: ...Installation Commissioning 58 Senscient ELDS Rev 15 GB 2 x Mounting Brackets ...
Страница 140: ...Certification 140 Senscient ELDS Rev 15 GB 9 1 2 Control Drawing CENELEC ATEX ...
Страница 142: ...Certification 142 Senscient ELDS Rev 15 GB 9 1 4 Control Drawing CSA US Canada ...
Страница 158: ...Appendix D Manufacturer s EC Declarations 158 Senscient ELDS Rev 15 GB 13 Appendix D Manufacturer s EC Declarations ...
Страница 159: ...Appendix D Manufacturer s EC Declarations Senscient ELDS Rev 15 159 GB ...
Страница 160: ...Appendix D Manufacturer s EC Declarations 160 Senscient ELDS Rev 15 GB ...
Страница 184: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose ...